2020-10-23 10:32:42 | BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE. |
| |
| 1- SCOPE OF WORK IS NOT CLEAR. THE PERMIT APPLICATION |
| DESCRIBES "INSTALLATION OF PAVER, STOREFRONT, STAIRS |
| AND MONUMENT PER ATTACHED DRAWINGS". |
| ON THE OTHER HAND, THE DESCRIPTION OF WORK ON-THE |
| ARCHITECTURAL PLANS IS "EXTERIOR COURTYARD WORK, |
| COMPOSED OF NEW STAIRS, NEW RAMPS & SIGNAGE TO CREATE |
| ADDITIONAL OPEN AIR AREAS AT EXISTING PALM BEACH |
| ATLANTIC UNIVERSITY STUDENT CENTER DINING". |
| ARCHITECTURAL PLANS DON'T INCLUDE THE STOREFRONTS. I |
| FOUND THAT THERE IS A SEPARATE PERMIT APPLICATION |
| SUBMITTED FOR STOREFRONT REPLACEMENT (PERMIT |
| #20090997). ARE THESE THE SAME STOREFRONTS. IF SO, |
| PLEASE REVISE THE SCOPE ON THE PERMIT APPLICATION AND |
| STATE THAT STOREFRONT UNDER SEPARATE PERMIT #20090997. |
| THIS WILL HELP AVOID CONFUSION/CONFLICTS/DELAYS. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 2-SITE PLAN ON SHEET A1.0 SHOWS TWO NEW TRELLIS |
| STRUCTURES ON THE NORTH WEST COURT YARD. PROVIDE |
| COMPLETE DESIGN CRITERIA AND COMPLETE FRAMING PLANS, |
| DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF |
| THOSE STRUCTURES AS REQUIRED BY SEC. 1603.1.1 4 AND |
| SEC. 1603.1FBC-BUILDING RESPECTIVELY. |
| |
| 3- SHEET A4.2: |
| A)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW |
| HANDRAIL ON BOTH SIDES OF STAIRS AND RAMPS. SEC. 505.2 |
| FBC-ACCESSIBILITY. REVISE AS REQUIRED. |
| |
| B)DETAIL #13 EXTERIOR STAIR DETAIL: NEED TO SHOW |
| HANDRAIL ON BOTH SIDES. SEC. 505.2 FBC-ACCESSIBILITY. |
| REVISE AS REQUIRED. |
| |
| C)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW THE |
| TOP AND BOTTOM EXTENSION AT RAMP. AND PROVIDE DETAILS. |
| SEC. 505.10.1 FBC-ACCESSIBILITY. REVISE AS REQUIRED. |
| |
| D) DETAIL #14 AND DETAIL #17: THE BOTTOM EXTENSION AT |
| STAIRS NEED TO EXTEND AT THE SLOPE OF THE STAIR FLIGHT |
| AS REQUIRED BY SEC. 505.10.3 FBC-ACCESSIBILITY. REVISE |
| AS REQUIRED. |
| |
| 4- SHEET A4.3: |
| A)DETAIL #22 EXTERIOR STAIR & PLANTER SECTION: HANDRAIL |
| HEIGHT OF 2'-8" DOESN'T COMPLY WITH SEC. 505.4 |
| FBC-ACCESSIBILITY. REVISE AS REQUIRED. |
| |
| B)DETAIL #21 EXTERIOR STAIR & PLANTER: NEED TO SHOW |
| HANDRAIL ON BOTH SIDES OF STAIRS. SEC. 505.2 |
| FBC-ACCESSIBILITY. REVISE AS REQUIRED. |
| |
| C)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| SIGNAGE WALL AND THE LOW WALL ALONG THE RAMPS. PROVIDE |
| COMPLETE SPECS FOR FOOTINGS, INCLUDING SIZES |
| REINFORCEMENT, ETC. AND WALL VERTICAL REINFORCEMENT. |
| SEC. 1603.1 FBC-BUILDING. |
| |
| D)DETAIL #24 EXTERIOR RAMP SECTION DETAIL: THIS DETAIL |
| DOESN'T MATCH WHAT IS SHOWN ON PLAN DETAIL #23 EXTERIOR |
| RAMP DETAIL. REVISE AS REQUIRED TO MATCH. ALSO, SHOW |
| THE HANDRAIL BOTTOM EXTENSION. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |