Plan Review Notes
Plan Review Notes For Permit 20090969
Permit Number 20090969
Review Stop B
Sequence Number 1
Notes
Date Text
2020-10-08 14:51:04AWNING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE SPECIFIC FOOTING DETAILS - DEPTH IN
 GRADE, CONCRETE REINFORCEMENT ETC.
 2) PLEASE SHOW COMPLIANCE WITH FBC 3105.3.4.1 FABRIC
 USED FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL MEET
 THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701
 OR HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN
 TESTED IN ACCORDANCE WITH ASTM E84 OR UL 723.
  