2020-10-08 14:51:04 | AWNING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE PROVIDE SPECIFIC FOOTING DETAILS - DEPTH IN | | GRADE, CONCRETE REINFORCEMENT ETC. | | 2) PLEASE SHOW COMPLIANCE WITH FBC 3105.3.4.1 FABRIC | | USED FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL MEET | | THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 | | OR HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN | | TESTED IN ACCORDANCE WITH ASTM E84 OR UL 723. | | |
|