Plan Review Notes
Plan Review Notes For Permit 20090955
Permit Number 20090955
Review Stop P
Sequence Number 1
Notes
Date Text
2020-10-01 10:42:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20090955 2450 PRESIDENTIAL WAY # 805
  
 1ST REVIEW
 PLUMBING COMMENTS:
  
 1.PER WPB FBC 105.1 AND 105.2 (EXEMPTION NOTED IN
 105.2, PLUMBING NOTE 3 DOES NOT APPLY AS 2450
 PRESIDENTIAL WAY, UNIT 805 DOES NOT FALL UNDER ONE AND
 TWO FAMILY DWELLINGS), A PLUMBING PERMIT IS REQUIRED.
 APPLICATION FOR PLUMBING PERMIT SHALL BE SUBMITTED BY A
 CONTRACTOR LICENSED IN THE PLUMBING DISCIPLINE AS
 DESCRIBED IN 489.113(M) FS. GC IS NOT LICENSED TO
 PERFORM PLUMBING . A SUB-PERMIT FOR PLUMBING IS
 REQUIRED.
  
 2.A DRAWING SUBMITTED BY THE PLUMBER IS REQUIRED AND
 SHALL BE SIGNED AS REQUIRED BY WPB FBC 107.2.1. THE
 PLUMBING CONTRACTOR (QUALIFIER) THAT CREATED / HAS
 DRAWN THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN ON THE PLANS DRAWN.
  
 3.THE SUBMITTED SKETCH DOES NOT MEET THE REQUIREMENT OF
 DRAFTSMAN QUALITY PLANS. 107.2.1.3. QUALITY OF PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A 1/8TH INCH SCALE ON
 SUBSTANTIAL PAPER OR OTHER ACCEPTABLE MEDIUM. THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENT
 POLICY OTHER STANDARDS FOR THE PLANS AND SPECIFICATIONS
 IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM
 SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED
 TO RECORD MANAGEMENT. ELECTRONIC MEDIA MUST BE
 COMPATIBLE WITH THE ARCHIVE REQUIREMENTS OF FLORIDA
 STATUTES.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090955 2450 PRESIDENTIAL WAY # 805