| RESIDENTIAL (R3) REVISION BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- PROVIDE KEY PLAN SHOWING SIZE AND LOCATION OF |
| WINDOWS TO BE INSTALLED. CLEARLY SPECIFY THE ROOM WHERE |
| WINDOW IS GOING TO BE INSTALLED. FOR EXAMPLE BEDROOM, |
| LIVING AREA, ETC. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 2-DESIGN PRESSURES OF PRODUCT APPROVAL FL19703-R4 |
| SUBMITTED ARE TOO LOW. NEED TO PROVIDE PRODUCT APPROVAL |
| OF WINDOW THAT MEETS THE DESIGN PRESSURES FOR BUILDING |
| LOCATED IN EXPOSURE "C". SEC. 702.6 FBC-EXISTING |
| BUILDING AND SEC. R301.2.1.4 FBC-RESIDENTIAL. |
| |
| 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| |
| 4- WINDOW PRODUCT APPROVAL SUBMITTED IS FOR NON-IMPACT |
| WINDOWS. NEED TO PROVIDE IMPACT PROTECTION AS REQUIRED |
| BY SEC. 702.6 FBC-EXISTING BUILDING AND SEC. R301.2.1.2 |
| FBC-RESIDENTIAL. |
| PROVIDE PRODUCT APPROVAL FOR WINDOW WITH IMPACT GLAZING |
| OR PROVIDE SHUTTERS PRODUCT APPROVALS. NOTE: NEED |
| COMPLETE SHUTTERS INSTALLATION SCHEDULE ALSO IF USING |
| SHUTTERS INSTEAD OF WINDOW WITH IMPACT GLAZING. |
| |
| 5-WINDOWS ARE NOT PART OF THE MASTER PERMIT. PROVIDE |
| THE VALUATION FOR THE ADDITIONAL SCOPE OF WORK. SEC. |
| 109.3 CITY AMENDMENTS. |
| |
| 6 COMMENTS ON REVISION #20031149 SUBMITTED ON |
| 03/24/2020 WERE NEVER ADDRESSED. NEED TO ADDRESS THIS |
| COMMENTS TO AVOID CONFLICTS/DELAYS. SEE COPY OF |
| COMMENTS BELOW. |
| |
| RESIDENTIAL (R3) REVISION BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTE: |
| BUILDING #2 SHOWS GUEST BEDROOM #1 AND GUEST BEDROOM |
| #2. SQUARE FOOTAGE TABLE ON SHEET A-01 SPECIFIES 468 |
| S.F. OF EXISTING AND PROPPED "ENCLOSED GARAGE". |
| "ENCLOSED GARAGE" IS NOT CONSIDERED A LIVABLE SPACE. |
| ACCORDING TO CITY RECORDS AND PALM BEACH COUNTY |
| PROPERTY APPRAISER THIS AREA IS A GARAGE NOT LIVABLE |
| AREA. THERE ARE NOT PERMITS FOR THE CONVERSION OF |
| GARAGE TO LIVABLE SPACE. BASED ON THE SCOPE OF WORK |
| SHOWN ON PLANS, THIS IS A CHANGE OF USE FROM GARAGE TO |
| LIVABLE SPACE. THIS IS A CHANGE OF OCCUPANCY SEC. 506 |
| FBC-EXISTING BUILDING. ALSO, THIS IS ALTERATION LEVEL |
| 3. SEC. 505 FBC-EXISTING BUILDING. |
| |
| (1)- NEW BEDROOMS: SPECIFY THE SIZE AND TYPE OF THE |
| PROPOSED BEDROOM WINDOWS TO VERIFY COMPLIANCE WITH THE |
| EGRESS REQUIREMENTS. SEC. R310.2.1 FBC-RESIDENTIAL AND |
| SEC. 801.3 FBC-EXISTING BUILDING. |
| |
| (2)- NEW BATHROOMS: SHOW COMPLIANCE WITH THE REQUIRED |
| FIXTURES SPACES AS REQUIRED BY SEC. R307 |
| FBC-RESIDENTIAL AND SEC. 801.3 FBC-EXISTING BUILDING. |
| SPECIFY THE MINIMUM CLEARANCES BETWEEN FIXTURES. |
| |
| (3)- CONVERSION OF THE GARAGE TO LIVABLE AREA REQUIRES |
| PALM BEACH COUNTY ASSESSMENT FOR IMPACT FEES. |
| |
| IMPACT FEES - |
| PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL |
| (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK |
| OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. |
| PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT |
| AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE |
| QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE |
| FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD |
| MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |