Plan Review Notes For Permit 20090921 |
Permit Number |
20090921 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-09-23 10:56:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) WHAT IS THE INTENDED PURPOSE AND PRODUCT PROPSOED | | FOR THESE TENT STRUCTURE? | | | | PLEASE PROVIDE DETAILS | | | | | | | | 2) THERE ARE NO INTERIOR FLOOR LAYOUTS AND EXITS. | | | | PLEASE PROVIDE DETAILS. | | | | | | 3) THERE IS NO LIGHTING INDICATED. HOW WILL LIGHTING BE | | PROVIDED WITHIN THE TENTS? | | | | PLEASE PROVIDE DETAILS | | | | | | 4) THERE ARE NO TIE-DOWNS INDICATED. | | | | PLEASE PROVIDE DETAILS | | | | | | | | 5) THERE APPEARS TO BE A FENCE INDICATED. | | | | WHERE ARE THE EXITS ALONG THE FENCE, HOW MANY AND THE | | SIZE OF THESE EXITS? | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|