| APPROVED WITH PROVISO: |
| SUBMIT INFORMATION FOR REVIEW BEFORE INSPECTIONS TO |
| AVOID CONFLICTS/DELAYS |
| 1- REVISE ENERGY CALCULATIONS: |
| A) SUBMIT FORM R405-2017 NOT R405-2020. |
| B) PROVIDE COMPLETE/CORRECT INFORMATION. CORRECT |
| ADDRESS IS 702 42ND STREET NOT 704 42ND ST. AND PROVIDE |
| OWNER'S NAME, BUILDER'S NAME. JURISDICTION NUMBER (THIS |
| JURISDICTION IS 604700). |
| C) ITEM #1 ON PAGE 1 OF 4 IS INCORRECT. THIS IS |
| EXISTING CONSTRUCTION NOT NEW CONSTRUCTION. |
| D) ITEM #10 ON PAGE 1 OF 4 IS MISSING THE WALL TYPE FOR |
| NEW BEDROOM. SEE PLANS AND REVISE AS REQUIRED. |
| E) PROVIDE THE NAME OF PERSON PERFORMING THE ANALYSIS |
| AND GENERATING THE REPORT AS REQUIRED BY SEC. |
| R405.4.2.1 FBC- ENERGY CONSERVATION. |
| F) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. THERE |
| ARE NO DOORS ON THE EAST SIDE OF THIS HOUSE. SEE NORTH |
| ARROW ON PLANS. ALSO, THERE ARE NO WOOD DOORS. SEE |
| PRODUCT APPROVAL SUBMITTED AND REVISE AS REQUIRED. |
| G) WINDOWS ORIENTATION ON PAGE 3 OF 4 IS INCORRECT. |
| COORDINATE WITH ITEM ABOVE. |
| H) THE HOME ADDRESS SHOWN ON THE EPL DISPLAY CARD |
| SUBMITTED IS INCORRECT. |
| THE CORRECT ADDRESS IS 702 42ND STREET NOT 704 42ND ST. |
| REVISE AS REQUIRED. |
| |
| |
| |
| |