2021-04-09 13:32:19 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| PERMIT #20090919 |
| |
| |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| |
| |
| |
| ORIGINAL COMMENT: |
| 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 505, |
| SEC. 506 FBC-EXISTING BUILDING AND SEC. R101.5 |
| FBC-ENERGY CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| RESPONSE: |
| 1(A)FORM SUBMITTED WAS CHANGED. FORM R405-2020 |
| SUBMITTED NOW IS FOR THE 2020 FBC. THIS PERMIT |
| APPLICATION IS REVIEWED UNDER TH 2017 FBC. NEED TO |
| PROVIDE CORRECT FORM R405-2017. |
| NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| 1(B) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| FORM. THE CORRECT ADDRESS IS 702 42ND STREET NOT 704 |
| 42ND ST. REVISE AS REQUIRED. |
| ALSO, PROVIDE OWNER'S NAME. PROVIDE BUILDER'S NAME. |
| SPECIFY JURISDICTION NUMBER (THIS JURISDICTION IS |
| 604700). SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| 1(C)ITEM #1 ON PAGE 1 OF 4 IS INCORRECT. THIS IS NOT |
| NEW CONSTRUCTION. THIS IS EXISTING CONSTRUCTION. SEE |
| PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| 1(D)ITEM #10 ON PAGE 1 OF 4 IS MISSING THE WALL TYPE |
| FOR NEW BEDROOM. SEE PLANS AND REVISE AS REQUIRED. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| 1(E) PROVIDE THE NAME OF PERSON PERFORMING THE ANALYSIS |
| AND GENERATING THE REPORT AS REQUIRED BY SEC. |
| R405.4.2.1 FBC- ENERGY CONSERVATION. |
| |
| 1(F) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT. |
| THERE ARE NO DOORS ON THE EAST SIDE OF THIS HOUSE. SEE |
| PLANS AND REVISE AS REQUIRED. |
| NOTE: TYPICALLY, IS A STANDARD PRACTICE TO DRAW PLANS |
| WITH NORTH ARROW FACING UP. ARCHITECT DREW FLOOR PLAN |
| ON SHEET A1.0 WITH NORTH ARROW POINTING DOWN (SOUTH). |
| THAT MAY BE WHY PERSON DOING THE CALCULATIONS GOT |
| MISLED. |
| ALSO, THERE ARE NO WOOD DOORS. SEE PRODUCT APPROVAL |
| SUBMITTED AND REVISE AS REQUIRED. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| 1(G)WINDOWS ORIENTATION ON PAGE 3 OF 4 IS INCORRECT. |
| REVISE WINDOWS ORIENTATION TO MATCH PLANS. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| NOTE: TYPICALLY, IS A STANDARD PRACTICE TO DRAW PLANS |
| WITH NORTH ARROW FACING UP. ARCHITECT DREW FLOOR PLAN |
| ON SHEET A1.0 WITH NORTH ARROW POINTING DOWN (SOUTH). |
| THAT MAY BE WHY PERSON DOING THE CALCULATIONS GOT |
| MISLED. |
| |
| 1(H)THE HOME ADDRESS SHOWN ON THE EPL DISPLAY CARD |
| SUBMITTED IS INCORRECT. |
| THE CORRECT ADDRESS IS 702 42ND STREET NOT 704 42ND ST. |
| REVISE AS REQUIRED. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| 2- OK |
| 3- OK |
| |
| ORIGINAL COMMENT: |
| 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| RESPONSE: |
| ARCHITECT'S RESPONSE LETTER IS MISSING THE PRODUCT |
| APPROVALS FOR THE EXTERIOR DOORS AND WINDOW MULLIONS |
| PRODUCT APPROVALS SUBMITTED. |
| |
| 5- OK |
| 6- OK |
| 7- OK |
| 8- OK |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |