Plan Review Notes
Plan Review Notes For Permit 20090919
Permit Number 20090919
Review Stop M
Sequence Number 2
Notes
Date Text
2020-12-31 10:40:262ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20090919
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE RESPOND TO NOTE 3 OF 1ST CYCLE REVIEW. PLEASE
 PROVIDE MECHANICAL EQUIPMENT SIZING CALCULATIONS. IS
 THIS GOING TO BE A NEW MECHANICAL UNIT UPSIZED TO
 HANDLE THE ADDITION MECHANICAL LOAD? IS THE EXISTING
 UNIT LARGE ENOUGH TO HANDLE THE ADDITIONAL LOAD OF THE
 NEW CONDITIONED SPACE? PLEASE SHOW THE SIZING
 CALCULATIONS AND ANSWER THESE QUESTIONS. FBC 107.2.1
  
 2) SHEET A1.1: PLEASE REFERENCE THE CURRENT EDITION OF
 THE FLORIDA BUILDING CODE IN THE NOTES. 2017 EDITION.
 FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  