2021-01-07 16:57:25 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 505, |
| SEC. 506 FBC-EXISTING BUILDING AND SEC. R101.5 |
| FBC-ENERGY CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| RESPONSE: |
| 1(A)OWNER OR OWNER'S ARCHITECT OR OTHER OWNER LEGALLY |
| AUTHORIZED AGENT NEEDS TO SIGN AND DATE THE BOTTOM OF |
| FORM AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| NOTE: PERMIT CAN NOT BE ISSUED WITHOUT THE OWNER'S OR |
| AUTHORIZED AGENT CERTIFICATION. |
| |
| |
| 1(B)BUILDER NAME DOESN'T MATCH BUILDER APPLYING FOR THE |
| WORK. REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.1 |
| FBC-ENERGY CONSERVATION. |
| |
| 2- OK |
| 3- OK |
| |
| ORIGINAL COMMENT: |
| 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| RESPONSE: |
| THERE IS NO WAY OF KNOWING WHICH PRODUCT APPROVALS THE |
| ARCHITECT REVIEWED/APPROVED. PRODUCT APPROVALS |
| SUBMITTED DON'T SHOW ANY INDICATION THAT THEY WERE |
| REVIEWED AND APPROVED BY THE ARCHITECT OF RECORD. THE |
| ONLY RESPONSE FROM ARCHITECT WAS "SEE APPROVED PRODUCT |
| APPROVALS FOR INSTALLATION". THERE IS NO REVIEW STAMP |
| ON THE PRODUCT APPROVAL OR ANY LIST OF SPECIFIC PRODUCT |
| APPROVAL NUMBERS AND MODELS THAT WERE REVIEWED/APPROVED |
| BY THE ARCHITECT. |
| ARCHITECT TO PROVIDE REVIEW STAMP ON EACH PRODUCT |
| APPROVAL OR PROVIDE LETTER CLEARLY LISTING EACH PRODUCT |
| APPROVAL SPECIFIC NUMBER AND MODEL. |
| |
| 5- OK |
| 6- OK |
| 7- OK |
| 8- OK |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |