Date |
Text |
2020-10-05 11:44:55 | 10/05/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED |
| CONTRACT PER THE WPB AMENDMENTS TO THE FBC 109.3. |
| BUILDING PERMITS VALUATIONS. |
| |
| 2. SIGNED AND SEALED DRAWINGS NEED TO BE |
| DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - |
| IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE |
| ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN |
| REVIEW REQUEST FORM" EXPLAINING THE REASON FOR |
| SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW |
| REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND |
| ASKING FOR THE FORM. |
| |
| 3. THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| AND DOCUMENTS: A FLOOR PLAN OF THE DEMOLITION PER THE |
| 2017 FBC WPB AMENDMENTS SEC. 107.3.5 MINIMUM PLAN |
| REVIEW CRITERIA FOR BUILDINGS. |
| |
| 4. PLEASE PROVIDE A NARRATIVE OF THE SCOPE OF WORK ON |
| PLANS FOR WORK BEING DONE ON BATHROOM AND ON |
| APPLICATION PER THE WPB FBC 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 5. SUBMIT A SLAB REPAIR DETAIL PLEASE SHOW THE WIDTH OF |
| THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO BE |
| REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE |
| AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH |
| INTO THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE |
| DOWELS, AND THE SPACING OF THE DOWELS ON CENTER. THE |
| REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL |
| AND THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED |
| SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| FOR A FINAL INSPECTION. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |