2020-10-16 14:03:25RESIDENTIAL R3)BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 505,
 SEC. 506 FBC-EXISTING BUILDING AND SEC. R101.5
 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 2-WINDOWS (37X53) FOR THE NEW BEDROOM WINDOWS DON'T
 COMPLY WITH THE MIN. CLEAR OPENING HEIGHT REQUIRED FOR
 EGRESS SEC. R310.2.1 FBC-RESIDENTIAL. NOTE: DESIGN
 PROFESSIONAL DOESN'T SPECIFY TYPE OF WINDOW. I AM
 ASSUMING THEY ARE SINGLE HUNG WINDOWS BASED ON THE
 PRODUCT APPROVALS SUBMITTED. ARCHITECT TO SPECIFY THE
 TYPE OF EGRES WINDOW AND REVISE SIZE AS REQUIRED.
 SEC. 506 FBC-EXISTING BUILDING AND SEC. 1012.4.1
 FBC-EXISTING
  
 3- WINDOW REPLACEMENT: CLEARLY SPECIFY TYPE AND SIZE OF
 EXISTING WINDOWS AND TYPE AND SIZE OF PROPOSED WINDOWS
 TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF
 SEC. 702.5 FBC-EXISTING BUILDING.
  
 NOTE: NEED TO VERIFY MANUFACTURER'S LARGEST STANDARD
 SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR
 EXISTING ROUGH OPENING AND THAT WILL NOT REDUCE THE
 EGRESS SIZE OPENING OF EXISTING WINDOW AS REQUIRED BY
 SEC. 702.5 FBC-EXISTING BUILDING.
  
 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 5- DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON FLOOR
 PLAN ON SHEET A1.0 ARE INCORRECT. THE DESIGN PRESSURES
 ARE TOO LOW BASED ON THE "C" EXPOSURE SPECIFIED ON
 SHEET T. ALSO, BOTH PRESSURES ARE SHOWN AS POSITIVE
 PRESSURES. THEY SHOULD BE POSITIVE AND NEGATIVE DESIGN
 PRESSURES. REVISE AS REQUIRED. SEC. 505, SEC. 506
 FBC-EXISTING BUILDING AND SEC. R301.2.1 FBC-RESIDENTIAL
  
 6- WALL SECTION ON SHEET A1.0:
 A)ARCHITECT TO SPECIFY CEILING INSULATION AND WALL
 INSULATION.
 NOTE: COORDINATE WITH THE ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS.
 SEC. 505, SEC. 506 FBC-EXISTING BUILDING AND SEC.
 R103.2 FBC-ENERGY CONSERVATION.
  
 B)ARCHITECT TO SPECIFY HOW ARE THE 2X TOP PLATES
 ATTACHED TO THE EXISTING STRUCTURE (BEAM)?. CLEARLY
 SPECIFY THE CONNECTOR.
 SEC. 505, SEC. 506 FBC-EXISTING BUILDING AND SEC.
 R301.2.1 FBC-RESIDENTIAL
  
 C)PROVIDE SPECIFICATIONS FOR THE STUCCO APPLICATION.
 ARCHITECT DOESN'T SPECIFY THE METAL LATH AND THE STUCCO
 THICKNESS. SEC. 505, SEC. 506 FBC-EXISTING BUILDING AND
 TABLE R702.1(1) FBC-RESIDENTIAL.
  
 D)THIS IS A CHANGE OF USE FROM CARPORT TO LIVABLE
 SPACE. TYPICALLY, CARPORTS ARE BUILT WITHOUT A FLOOR
 VAPOR BARRIER. ARCHITECT TO PROVIDE SPECIFICATIONS FOR
 THE CONCRETE SLAB VAPOR BARRIER AS REQUIRED BY SEC.
 R506.2.3 FBC-RESIDENTIAL.
 SEC. 505, SEC. 506 FBC-EXISTING BUILDING
  
 7- ACCORDING TO CITY RECORDS AND PALM BEACH COUNTY
 PROPERTY APPRAISER THE REAR ROOM OF THE HOUSE IS AN
 ENCLOSED PORCH NOT UTILITY ROOM. REVISE NAME ON THE
 FLOOR PLAN ON SHEET A1.0 AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 8- NEW BATHROOM SHOWN ON FLOOR PLAN ON SHEET A1.0:
 A)SPECIFY VENTILATION SHOWING COMPLIANCE WITH SEC
 R303.3 FBC-RESIDENTIAL.
 SEC. 505, SEC. 506 FBC-EXISTING BUILDING.
  
 B) SPECIFY ROOM DIMENSIONS SHOWING COMPLIANCE WITH SEC.
 R307 FBC-RESIDENTIAL.
 SEC. 505, SEC. 506 FBC-EXISTING BUILDING.
  
 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW
 BASED ON ALL THE SCOPE OF WORK SHOWN ON PLANS.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION TO INCLUDE ALL COSTS OR PROVIDE COPY OF
 SIGNED CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER