2020-10-16 14:03:25 | RESIDENTIAL R3)BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 505, |
| SEC. 506 FBC-EXISTING BUILDING AND SEC. R101.5 |
| FBC-ENERGY CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| 2-WINDOWS (37X53) FOR THE NEW BEDROOM WINDOWS DON'T |
| COMPLY WITH THE MIN. CLEAR OPENING HEIGHT REQUIRED FOR |
| EGRESS SEC. R310.2.1 FBC-RESIDENTIAL. NOTE: DESIGN |
| PROFESSIONAL DOESN'T SPECIFY TYPE OF WINDOW. I AM |
| ASSUMING THEY ARE SINGLE HUNG WINDOWS BASED ON THE |
| PRODUCT APPROVALS SUBMITTED. ARCHITECT TO SPECIFY THE |
| TYPE OF EGRES WINDOW AND REVISE SIZE AS REQUIRED. |
| SEC. 506 FBC-EXISTING BUILDING AND SEC. 1012.4.1 |
| FBC-EXISTING |
| |
| 3- WINDOW REPLACEMENT: CLEARLY SPECIFY TYPE AND SIZE OF |
| EXISTING WINDOWS AND TYPE AND SIZE OF PROPOSED WINDOWS |
| TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF |
| SEC. 702.5 FBC-EXISTING BUILDING. |
| |
| NOTE: NEED TO VERIFY MANUFACTURER'S LARGEST STANDARD |
| SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR |
| EXISTING ROUGH OPENING AND THAT WILL NOT REDUCE THE |
| EGRESS SIZE OPENING OF EXISTING WINDOW AS REQUIRED BY |
| SEC. 702.5 FBC-EXISTING BUILDING. |
| |
| 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 5- DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON FLOOR |
| PLAN ON SHEET A1.0 ARE INCORRECT. THE DESIGN PRESSURES |
| ARE TOO LOW BASED ON THE "C" EXPOSURE SPECIFIED ON |
| SHEET T. ALSO, BOTH PRESSURES ARE SHOWN AS POSITIVE |
| PRESSURES. THEY SHOULD BE POSITIVE AND NEGATIVE DESIGN |
| PRESSURES. REVISE AS REQUIRED. SEC. 505, SEC. 506 |
| FBC-EXISTING BUILDING AND SEC. R301.2.1 FBC-RESIDENTIAL |
| |
| 6- WALL SECTION ON SHEET A1.0: |
| A)ARCHITECT TO SPECIFY CEILING INSULATION AND WALL |
| INSULATION. |
| NOTE: COORDINATE WITH THE ENERGY CALCULATIONS TO AVOID |
| CONFLICTS/DELAYS. |
| SEC. 505, SEC. 506 FBC-EXISTING BUILDING AND SEC. |
| R103.2 FBC-ENERGY CONSERVATION. |
| |
| B)ARCHITECT TO SPECIFY HOW ARE THE 2X TOP PLATES |
| ATTACHED TO THE EXISTING STRUCTURE (BEAM)?. CLEARLY |
| SPECIFY THE CONNECTOR. |
| SEC. 505, SEC. 506 FBC-EXISTING BUILDING AND SEC. |
| R301.2.1 FBC-RESIDENTIAL |
| |
| C)PROVIDE SPECIFICATIONS FOR THE STUCCO APPLICATION. |
| ARCHITECT DOESN'T SPECIFY THE METAL LATH AND THE STUCCO |
| THICKNESS. SEC. 505, SEC. 506 FBC-EXISTING BUILDING AND |
| TABLE R702.1(1) FBC-RESIDENTIAL. |
| |
| D)THIS IS A CHANGE OF USE FROM CARPORT TO LIVABLE |
| SPACE. TYPICALLY, CARPORTS ARE BUILT WITHOUT A FLOOR |
| VAPOR BARRIER. ARCHITECT TO PROVIDE SPECIFICATIONS FOR |
| THE CONCRETE SLAB VAPOR BARRIER AS REQUIRED BY SEC. |
| R506.2.3 FBC-RESIDENTIAL. |
| SEC. 505, SEC. 506 FBC-EXISTING BUILDING |
| |
| 7- ACCORDING TO CITY RECORDS AND PALM BEACH COUNTY |
| PROPERTY APPRAISER THE REAR ROOM OF THE HOUSE IS AN |
| ENCLOSED PORCH NOT UTILITY ROOM. REVISE NAME ON THE |
| FLOOR PLAN ON SHEET A1.0 AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 8- NEW BATHROOM SHOWN ON FLOOR PLAN ON SHEET A1.0: |
| A)SPECIFY VENTILATION SHOWING COMPLIANCE WITH SEC |
| R303.3 FBC-RESIDENTIAL. |
| SEC. 505, SEC. 506 FBC-EXISTING BUILDING. |
| |
| B) SPECIFY ROOM DIMENSIONS SHOWING COMPLIANCE WITH SEC. |
| R307 FBC-RESIDENTIAL. |
| SEC. 505, SEC. 506 FBC-EXISTING BUILDING. |
| |
| 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW |
| BASED ON ALL THE SCOPE OF WORK SHOWN ON PLANS. |
| VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S |
| OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS |
| REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE |
| VALUATION TO INCLUDE ALL COSTS OR PROVIDE COPY OF |
| SIGNED CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |