Plan Review Notes
Plan Review Notes For Permit 20090918
Permit Number 20090918
Review Stop E
Sequence Number 1
Notes
Date Text
2020-10-09 17:18:06ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE OF PERMIT IS TO REFLECT ALL MATERIALS,
 EQUIPMENT AND LABOR FOR A COMPLETE SYSTEM (3100)
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) ATS ARE THEY SERVICE ENTRANCE RATED?
  
 3) 10 X 10 GUUTER AT SERVICE HOW MANY CONDUCTORS ARE
 GOING TO BE IN THIS GUTTER?
  
 4) FEEDER TAP OFF GENERATOR WHICH SECTION DOES IT
 COMPLY WITH IN 240.21?
  
 5) GROUNDING ELECTRODE SHOWN DOES NOT MEET THE CODE IT
 IS EITHER DONE IN THE LINE GITTER AT THE TOP OR IN EACH
 INDIVIDUAL DISCONNECT UNDER THE GUTTER. 250.64(D)
  
 6) SHOW LOCATION OF THE GUTTER AT THE SERVICE IN
 RELATION TOO THE GENERATOR (DISTANCE)
  
 7) FEEDER OF 400A TRANSFER SWICH ONLY 4/0 CONDUCTORS?
  
 8) LOADS BEING FED BY GERNERATOR? LOAD CALCULATION
 REQUIRED.
  
 9) IS THIS LEGALLY REQUIRED SYSTEM? PER 702.
  
  