 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 107.2.1, PLEASE CONFIRM THAT THE WIDTH OF THE
 GENERATOR SLAB IS ACCEPTABLE TO MEET THE REQUIREMENTS
 OF THE MANUFACTURER'S SPECIFICATIONS AS THE GENERAC
 SPECIFICATION NOTES RECOMMEND A 49" WIDTH AND THE
 SUBMITTED PAD INFORMATION IS FOR A 46" WIDTH.
 2) FBC B/WPB AMENDMENTS 109.3, PLEASE PROVIDE A COST
 BREAK DOWN OF THE VALUATION OF THE JOB.
 3) FBC B 107.2.5, PLEASE PROVIDE A SITE PLAN INDICATING
 THE SET BACK MEASUREMENTS INCLUDING THE LOCATIONS OF
 ADJACENT STRUCTURES.
 4) FBC B/WPB AMENDMENTS 107.1, PLEASE PROVIDE
 VERIFFIABLE ENGINEER'S SIGNATURE AND SEAL ON GENERATOR
 PAD ENGINEERING SHEET.