2020-09-28 13:54:48 | 09/28/20 1ST PLUMBING/POOL REVIEW**DENIED** WITH |
| COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. SHEET ONE ON FILTER EQUIPMENT SIZE IT CALLS FOR 200 |
| SF AND YOU SPEC OUT CS 150 WHICH IS 150 SF PLEASE |
| CLARIFY OR CHANGE TO MATCH PLANS PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 2. SHEET ONE FOR PUMP EQUIPMENT SIZE CALLS FOR A |
| VSFHP165JEP YOU HAVE SPECS FOR A VSFHP185DV2A PLEASE |
| CLARIFY OR CHANGE TO MATCH PLANS PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 3. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR |
| THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| |
| 4. THE PLANS ARE VERY BLURRY AND MOST NUMBERS CAN?T BE |
| MADE OUT SO PLEASE SUBMIT LEGIBLE PLANS PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 5. ALL PAGES NEED TO HAVE A DIGITAL SIGNATURE PER THE |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.005. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |