2020-12-01 16:29:252ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20090894
 12/1/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P2 & P3: THE DRINKING FOUNTAIN FIXTURE SHALL
 CONNECT TO THE 4 IN. DRAIN AT A POINT DOWNSTREAM OF THE
 WATER CLOSET AND THE BATHROOM WET VENT SYSTEM- SECTION
 912.1 FBC P.
  
 2) P1 & P3: PLEASE LABEL THE HWR LINE FOR CLARITY-
 SECTION 107.2.1 WPB.
  
 3) P1 & P3: PROVIDE KEYNOTE #2 TMV AT ALL LAVATORY
 LOCATIONS- SECTION 416.5 FBC P.
  
 4) P3: PROVIDE A WATER HAMMER ARRESTOR FOR THE CW LINE
 TO THE DRINKING FOUNTAINS- SECTION 604.9 FBC P.
  
 5) P1, P2, P3: THE "TYPICAL WATER ISOMETRIC" SHOWS A
 WASHING MACHINE THAT IS NOT SHOWN ON THE OTHER PLUMBING
 DRAWINGS. PLEASE ADD THE WASHING MACHINE OR REMOVE IT
 FROM THE ISO- SECTION 107.2.1 WPB.
  
 6) P3 WATER HEATER DETAILS: PLEASE CORRECT THE DETAIL
 IN COMPLIANCE WITH SECTIONS 607.2.2 & 607.3 FBC P.
  
 A) SECTION 607.2.2: IT APPEARS THAT A MASTER TMV IS
 BEING INSTALLED WHICH REQUIRES THE HOT WATER OR
 TEMPERED WATER RETURN LINE SHALL BE ROUTED TO THE COLD
 WATER INLET PIPE OF THE WATER HEATER AND THE COLD WATER
 INLET PIPE OR THE HOT WATER RETURN CONNECTION OF THE
 THERMOSTATIC MIXING VALVE.
  
 B) SECTION 607.3: WHERE A STORAGE WATER HEATER IS
 SUPPLIED WITH COLD WATER THAT PASSES THROUGH A CHECK
 VALVE, PRESSURE REDUCING VALVE OR BACKFLOW PREVENTER
 (CHECK VALVE), A THERMAL EXPANSION CONTROL DEVICE SHALL
 BE CONNECTED TO THE WATER HEATER COLD WATER SUPPLY PIPE
 AT A POINT THAT IS DOWNSTREAM OF ALL CHECK VALVES,
 PRESSURE REDUCING VALVES AND BACKFLOW PREVENTERS.
 THERMAL EXPANSION CONTROL DEVICES SHALL BE SIZED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS AND
 SHALL BE SIZED SUCH THAT THE PRESSURE IN THE WATER
 DISTRIBUTION SYSTEM SHALL NOT EXCEED THAT REQUIRED BY
 SECTION 604.8. PLEASE NOTE THAT PRESSURE OR TEMPERATURE
 RELIEF VALVES SHALL NOT BE USED AS A MEANS OF
 CONTROLLING THERMAL EXPANSION- SECTION 504.4 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  