2020-12-01 16:29:25 | 2ND REVIEW FBC-2017 PLUMBING |
| PERMIT- 20090894 |
| 12/1/2020 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS P2 & P3: THE DRINKING FOUNTAIN FIXTURE SHALL |
| CONNECT TO THE 4 IN. DRAIN AT A POINT DOWNSTREAM OF THE |
| WATER CLOSET AND THE BATHROOM WET VENT SYSTEM- SECTION |
| 912.1 FBC P. |
| |
| 2) P1 & P3: PLEASE LABEL THE HWR LINE FOR CLARITY- |
| SECTION 107.2.1 WPB. |
| |
| 3) P1 & P3: PROVIDE KEYNOTE #2 TMV AT ALL LAVATORY |
| LOCATIONS- SECTION 416.5 FBC P. |
| |
| 4) P3: PROVIDE A WATER HAMMER ARRESTOR FOR THE CW LINE |
| TO THE DRINKING FOUNTAINS- SECTION 604.9 FBC P. |
| |
| 5) P1, P2, P3: THE "TYPICAL WATER ISOMETRIC" SHOWS A |
| WASHING MACHINE THAT IS NOT SHOWN ON THE OTHER PLUMBING |
| DRAWINGS. PLEASE ADD THE WASHING MACHINE OR REMOVE IT |
| FROM THE ISO- SECTION 107.2.1 WPB. |
| |
| 6) P3 WATER HEATER DETAILS: PLEASE CORRECT THE DETAIL |
| IN COMPLIANCE WITH SECTIONS 607.2.2 & 607.3 FBC P. |
| |
| A) SECTION 607.2.2: IT APPEARS THAT A MASTER TMV IS |
| BEING INSTALLED WHICH REQUIRES THE HOT WATER OR |
| TEMPERED WATER RETURN LINE SHALL BE ROUTED TO THE COLD |
| WATER INLET PIPE OF THE WATER HEATER AND THE COLD WATER |
| INLET PIPE OR THE HOT WATER RETURN CONNECTION OF THE |
| THERMOSTATIC MIXING VALVE. |
| |
| B) SECTION 607.3: WHERE A STORAGE WATER HEATER IS |
| SUPPLIED WITH COLD WATER THAT PASSES THROUGH A CHECK |
| VALVE, PRESSURE REDUCING VALVE OR BACKFLOW PREVENTER |
| (CHECK VALVE), A THERMAL EXPANSION CONTROL DEVICE SHALL |
| BE CONNECTED TO THE WATER HEATER COLD WATER SUPPLY PIPE |
| AT A POINT THAT IS DOWNSTREAM OF ALL CHECK VALVES, |
| PRESSURE REDUCING VALVES AND BACKFLOW PREVENTERS. |
| THERMAL EXPANSION CONTROL DEVICES SHALL BE SIZED IN |
| ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS AND |
| SHALL BE SIZED SUCH THAT THE PRESSURE IN THE WATER |
| DISTRIBUTION SYSTEM SHALL NOT EXCEED THAT REQUIRED BY |
| SECTION 604.8. PLEASE NOTE THAT PRESSURE OR TEMPERATURE |
| RELIEF VALVES SHALL NOT BE USED AS A MEANS OF |
| CONTROLLING THERMAL EXPANSION- SECTION 504.4 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |