Plan Review Notes
Plan Review Notes For Permit 20090894
Permit Number 20090894
Review Stop E
Sequence Number 1
Notes
Date Text
2020-11-02 10:27:18CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) THERE ARE SOME DISCREPANCIES REGARDING THE NUMBER
 AND LOCATION OF AHUS AND A/C UNITS ON THE DRAWINGS: E5
 SHOWS TWO AHU AND TWO A/C UNITS ON PANEL SCHEDULES, E1
 SHOWS THREE AHUS AND ONE A/C, E7 SHOWS ONE UNIT AND
 MECHANICAL SHEET M1 SHOWS ONE UNIT E7. PLEASE CLARIFY
 AND ADJUST DRAWINGS, PANEL SCHEDULES AND CALCULATIONS
 AS REQUIRED. FBC 107.
  
 2) ALL OF A/C AND AHUS SHOULD HAVE ONE GFCI RECEPTACLE
 WITHIN 25 FEET. ONCE CORRECTIONS MENTIONED ABOVE ARE
 MADE PLEASE MAKE SURE TO INCLUDE THESE RECEPTACLES ON
 DRAWINGS. NEC 210.63.
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  