Plan Review Notes For Permit 20090894 |
Permit Number |
20090894 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-11-02 10:27:18 | CODES IN EFFECT | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1) THERE ARE SOME DISCREPANCIES REGARDING THE NUMBER | | AND LOCATION OF AHUS AND A/C UNITS ON THE DRAWINGS: E5 | | SHOWS TWO AHU AND TWO A/C UNITS ON PANEL SCHEDULES, E1 | | SHOWS THREE AHUS AND ONE A/C, E7 SHOWS ONE UNIT AND | | MECHANICAL SHEET M1 SHOWS ONE UNIT E7. PLEASE CLARIFY | | AND ADJUST DRAWINGS, PANEL SCHEDULES AND CALCULATIONS | | AS REQUIRED. FBC 107. | | | | 2) ALL OF A/C AND AHUS SHOULD HAVE ONE GFCI RECEPTACLE | | WITHIN 25 FEET. ONCE CORRECTIONS MENTIONED ABOVE ARE | | MADE PLEASE MAKE SURE TO INCLUDE THESE RECEPTACLES ON | | DRAWINGS. NEC 210.63. | | | | ENRIQUE QUINONEZ | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|