2020-10-21 09:54:35 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20090894 |
| ADD: 1100 25TH ST. |
| CONT: NORTHLAKE CONSTRUCTION CO. |
| TEL: 561-202-7044 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. OCT. 21ST/ 2020 |
| ACTION: DENIED |
| |
| 1) THE STRUCTURAL SHEETS SHOW LARGER OVERHEAD DOOR |
| OPENINGS BEING MODIFIED. SHEET S-3 AND S-4 SHOW THE |
| EXISTING AND PROPOSED NEW OVERHEAD DOOR OPENINGS. NONE |
| OF THE STRUCTURAL PLANS PROVIDE THE WIND DESIGN |
| CRITERIA FOR THESE OPENINGS. |
| 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| |
| 1.2. RISK CATEGORY. |
| |
| 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| |
| 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| THE DESIGN OF THE STRUCTURE, PSF. |
| |
| 1.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| CONVERSION VULT TO VASD. |
| |
| 2A) THE PRODUCT APPROVAL SUBMITTED FL 19313-R1 |
| MANUFACTURER ROLLING DOOR HAS NOT BEEN REVIEWED BY THE |
| DESIGNER OF RECORD. W. P. B. 107.3.4. PRODUCT |
| APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY |
| FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE |
| REVIEWED AND APPROVED IN WRITING(SHOP DRAWING STAMP OF |
| APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 2B) NEITHER THE CONTRACTOR NOR THE DESIGNER OF RECORD |
| HAS INDICATED WITHIN THE PRODUCT APPROVAL REPORT # FL |
| 19313R-1 WHICH SLAT IS GOING TO BE INSTALLED SLAT 1 OR |
| SLAT 1A, SEE PAGE 3 OF 6 IN THE TECHNICAL SHEETS. |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3) SHEET S-4 WEST ELEVATIONS, CLARIFICATION NEEDED, IT |
| WOULD APPEAR THERE IS A EXISTING UPPER TIE BEAM AND |
| LOWER TIE BEAM. THE PLANS INDICATE TO CUT 4 FEET FROM |
| THE OVERALL TIE BEAM. NOTE STATES THE CONTRACTOR IS TO |
| X-RAY AND CONFIRM AT LEAST 3 LEVELS OF STEEL TIED INTO |
| COLUMNS ON BOTH SIDES. THE QUESTION IS THE LOWER TIE |
| BEAM WOULD HAVE NORMALLY BEEN DESIGNED WITH HOOPS TO |
| CARRY THE LOADS OVER THE DOOR OPENING. THE CONCERN IS |
| IF THERE IS NO HOOPS OR STIRRUPS IN THE UPPER BEAM, |
| WILL VERIFICATION OF THE NUMBER OF HORIZONTAL BARS BE |
| ENOUGH? IS THE WEST WALL CARRYING THE ROOF FRAMING |
| MEMBERS OR ARE THE ROOF FRAMING MEMBERS PARALLELING THE |
| WEST WALL WITH MINIMUM ROOF LOADING? 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED TO DETERMINE |
| VERIFICATION OF JOBSITE CONDITIONS. |
| |
| 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |