2021-02-11 12:48:22 | 1ST REVIEW FBC-2017 RES. FUEL GAS. |
| PERMIT- 20090819 |
| 2/11/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) P PLAN: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW |
| WATER HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS- |
| SECTION G2448.1 FBC RES. PLEASE NOTE COMPLETE |
| SPECIFICATIONS AND INSTALLATION MANUAL SHALL BE ONSITE |
| AT TIME OF INSPECTION, AND THAT AN ADDITIONAL PRESSURE |
| REGULATOR MAY BE REQUIRED AT THE WATER HEATER BASED ON |
| MANUFACTURER'S INPUT PRESSURE SPECIFICATION. |
| |
| 2) P PLAN: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| NEW RANGE SHOWING BTUH LOAD AND INPUT PRESSURE- SECTION |
| G2447.1 FBC RES. PLACE A NOTE ON THE PLAN TO INDICATE |
| ACCESS SHALL BE PROVIDED TO THE APPLIANCE SHUTOFF |
| VALVE- G2450.5.1 FBC RES. |
| |
| 3) THE GAS CONTRACTOR OF RECORD WHO PREPARED THE GAS |
| RISER DRAWING SHALL SUBMIT A GAS SUB-PERMIT |
| APPLICATION- SECTION 105.1 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |