Plan Review Notes
Plan Review Notes For Permit 20090819
Permit Number 20090819
Review Stop G
Sequence Number 1
Notes
Date Text
2021-02-11 12:48:221ST REVIEW FBC-2017 RES. FUEL GAS.
 PERMIT- 20090819
 2/11/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P PLAN: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW
 WATER HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS-
 SECTION G2448.1 FBC RES. PLEASE NOTE COMPLETE
 SPECIFICATIONS AND INSTALLATION MANUAL SHALL BE ONSITE
 AT TIME OF INSPECTION, AND THAT AN ADDITIONAL PRESSURE
 REGULATOR MAY BE REQUIRED AT THE WATER HEATER BASED ON
 MANUFACTURER'S INPUT PRESSURE SPECIFICATION.
  
 2) P PLAN: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 NEW RANGE SHOWING BTUH LOAD AND INPUT PRESSURE- SECTION
 G2447.1 FBC RES. PLACE A NOTE ON THE PLAN TO INDICATE
 ACCESS SHALL BE PROVIDED TO THE APPLIANCE SHUTOFF
 VALVE- G2450.5.1 FBC RES.
  
 3) THE GAS CONTRACTOR OF RECORD WHO PREPARED THE GAS
 RISER DRAWING SHALL SUBMIT A GAS SUB-PERMIT
 APPLICATION- SECTION 105.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  