Plan Review Notes
Plan Review Notes For Permit 20090811
Permit Number 20090811
Review Stop P
Sequence Number 1
Notes
Date Text
2020-09-29 17:06:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20090811 1117 N OLIVE AVE # 101
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PER FBC 1210.2.2, WALLS AND PARTITIONS WITHIN 2 FEET
 (610 MM) OF SERVICE SINKS, URINALS AND WATER CLOSETS
 SHALL HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A
 HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE. PAINTED WALLS DO NOT COMPLY.
 REVISE THE ROOM FINISH SCHEDULE ON PLAN SHEET A-3 TO
 COMPLY.
  
 2.PROVIDE CLEAR FLOOR SPACE FOR BREAKROOM SINK. IF
 PARALLEL APPROACH, SINK SHALL BE CENTERED ON THE SPACE.
 IF FORWARD APPROACH, CABINET AND SINK SHALL BE
 CONSTRUCTED TO COMPLY WITH FBC ACC 306 FOR KNEE AND TOE
 CLEARANCE AND SHALL ACCOMMODATE THE FULL WIDTH OF THE
 REQUIRED 30 X 48 CLEAR FLOOR SPACE.
  
 3.PER FBC ACC 212.3, WHERE SINKS ARE PROVIDED, AT LEAST
 5 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED
 IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606.
 PROVIDE MINIMUM OF ONE ACCESSIBLE EXAM ROOM SINK AND
 PROVIDE CLEAR FLOOR SPACE FOR ACCESSIBLE SINK.
  
 4.PER WPB FBC 107.2.1, AS A DRINKING FOUNTAIN IS NOT
 REQUIRED BASED ON OCCUPANT LOAD AND NOT BEING PROVIDED,
 DELETE REFERENCES TO SAME ON PLAN SHEET A-3.
  
 5.PER WPB FBC 107.2.1, CLARIFY THE WATER CLOSET SHALL
 BE POSITIONED WITH A WALL OR PARTITION TO THE REAR AND
 TO ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL
 BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE
 WALL OR PARTITION PER FBC ACC 604.2
  
 6.PER WPB FBC 107.2.1, CLARIFY TOILET PAPER DISPENSERS
 SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48
 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE
 LOCATED BEHIND GRAB BARS PER FBC ACC 604.8.
  
 7.PLEASE NOTE THAT THE IN-LINE VALVE FOR THE HOT WATER
 RESTROOM WHEN IN THE OFF POSITION EFFECTIVELY KILLS THE
 HOT WATER RECIRCULATION. PROVIDE DEDICATED VALVED HOT
 WATER DROP TO LAVATORY FROM RECIRCULATED LINE TO COMPLY
 WITH FBC PL 606.1.
  
 8.RE: WATER HEATER DETAIL
 A.PER FBC PL 607.3, WHERE A STORAGE WATER HEATER IS
 SUPPLIED WITH COLD WATER THAT PASSES THROUGH A CHECK
 VALVE, PRESSURE REDUCING VALVE OR BACKFLOW PREVENTER, A
 THERMAL EXPANSION CONTROL DEVICE SHALL BE CONNECTED TO
 THE WATER HEATER COLD WATER SUPPLY PIPE AT A POINT THAT
 IS DOWNSTREAM OF ALL CHECK VALVES, PRESSURE REDUCING
 VALVES AND BACKFLOW PREVENTERS. THERMAL EXPANSION
 CONTROL DEVICES SHALL BE SIZED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS AND SHALL BE SIZED SUCH
 THAT THE PRESSURE IN THE WATER DISTRIBUTION SYSTEM
 SHALL NOT EXCEED THAT REQUIRED BY SECTION 604.8.
 B.PER FBC PL 504.6, PROVIDE AN AIR GAP FOR THE T & P
 RELIEF DISCHARGE TO THE PAN.
 C.PER FBC PL 504.2, BOTTOM FED WATER HEATERS AND BOTTOM
 FED TANKS CONNECTED TO WATER HEATERS SHALL HAVE A
 VACUUM RELIEF VALVE INSTALLED. THE VACUUM RELIEF VALVE
 SHALL COMPLY WITH ANSI Z21.22.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS OR DIGITALLY SIGNED AND SEALED
 BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090811 1117 N OLIVE AVE # 101
  