Plan Review Notes
Plan Review Notes For Permit 20090781
Permit Number 20090781
Review Stop G
Sequence Number 2
Notes
Date Text
2020-10-05 13:23:261ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090781
 9/24/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE APPROVED GENERATOR PERMIT AND PLANS UNDER
 PERMIT- 20080051 WAS FOR A 27 KW GENERATOR. PLEASE
 CORRECT THE RISER TO SHOW THE CORRECT 359,000 BTUH LOAD
 AS INDICATED IN THE GENERATOR SPECS SUBMITTED WITH THE
 PERMIT.
  
 2) THE GENERATOR SPECS SHOW A NATURAL GAS INPUT
 PRESSURE OF 3.5- 7 IN. W.C. HOWEVER THE RISER DRAWING
 SHOWS A REGULATOR WITH A 11 IN. W.C DELIVERY PRESSURE
 TO THE GENERATOR. PLEASE CORRECT AND INDICATE THE MAKE
 AND MODEL OF THE SELECTED REGULATOR ON THE RISER.
 SUBMIT MARKED UP OR HIGHLIGHTED REGULATOR SPECS SHOWING
 THE MODEL, INLET AND OUTLET PRESSURES, SPRING
 SELECTION, AND ORIFICE SIZE- SECTION G2421.1 & G2421.2.
 SHOW THE REQUIRED PIPE UNIONS AT THE REGULATOR.
  
 3) THERE IS A 0 VALUE FOR THE PROPOSED GAS PIPING
 INSTALLATION. PLEASE SUBMIT A COPY OF A SIGNED CONTRACT
 AND/OR COPIES OF INVOICES AND ESTIMATES SHOWING THE
 TOTAL COST OF THE INSTALLATION INCLUDING VALUE OF
 LABOR, MATERIALS, EQUIPMENT, SITE WORK, DESIGN FEES,
 AND OVERHEAD AND PROFIT- SECTION 109.3 WPB. IF THE COST
 OF THE GAS INSTALLATION WAS INCLUDED IN THE GENERATOR
 PERMIT, PLEASE PROVIDE COPIES OF THE PRIMARY AND
 SUB-CONTRACTS TO VERIFY.
  
 4) PLEASE NOTE THE GENERATOR (UNDER SEPARATE PERMIT)
 SHALL BE INSTALLED A MINIMUM OF 5' AWAY FROM
 COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA 37, AND A MINIMUM OF
 10' FROM MECHANICAL OR GRAVITY AIR INTAKES (WINDOW AND
 DOOR OPENINGS) INTO THE BUILDING- SEC. R303.5.1 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  