Plan Review Notes
Plan Review Notes For Permit 20090781
Permit Number 20090781
Review Stop G
Sequence Number 1
Notes
Date Text
2020-09-24 11:14:001ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090781
 9/24/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS ISOMETRIC DRAWING:
  
 A) SHOW THE LENGTH, THE TYPE, AND SIZE OF PIPING FROM
 THE METER TO THE 1-1/2" TEE, FROM THE 1-1/2" TEE TO THE
 1-1/4" TEE, AND FROM THE 1-1/4" TEE TO THE PIPE
 ENTRANCE INTO THE BUILDING. PLEASE CLARIFY IF THE
 1-1/4" TEE IS A REDUCER FITTING AND NOT A TEE BECAUSE A
 SECOND BRANCH LINE IS NOT SHOWN ON THE RISER- SECTIONS
 G2413.4.1 FBC RES.
 B) SHOW THE LOCATIONS OF THE LOW PRESSURE REGULATORS
 FOR THE INTERIOR APPLIANCES AND THE POOL HEATER-
 SECTION G2421.1 & G2421.2 FBC RES.
 C) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. THE
 UPDATED SPECS FOR THE GENERAC 22KW MODEL INDICATE A
 FULL LOAD OF 306,000 BTUH FOR NATURAL GAS. PLEASE
 CORRECT THE LOAD SHOWN ON THE RISER.
 D) THE GENERAC SPECS SHOW A NATURAL GAS INPUT PRESSURE
 OF 3.5- 7 IN. W.C. HOWEVER THE RISER DRAWING SHOWS A
 REGULATOR WITH A 11 IN. W.C DELIVERY PRESSURE TO THE
 GENERATOR. PLEASE CORRECT AND INDICATE THE MAKE AND
 MODEL OF THE SELECTED REGULATOR ON THE RISER. SUBMIT
 MARKED UP OR HIGHLIGHTED REGULATOR SPECS SHOWING THE
 MODEL, INLET AND OUTLET PRESSURES, SPRING SELECTION,
 AND ORIFICE SIZE- SECTION G2421.1 & G2421.2. SHOW THE
 REQUIRED PIPE UNIONS AT THE REGULATOR.
 E) INDICATE HOW THE PE PIPING RISER WILL MAKE
 CONNECTION TO THE EXISTING PIPING AT THE BBQ- SECTIONS
 G2415.17.1 & G2415.17.2. PLEASE NOTE THAT SPECS FOR
 ANODELESS RISERS AND PE/METALLIC PIPE CONNECTORS SHALL
 BE LISTED AND LABELED.
 F) INDICATE A DRIP LEG WILL BE INSTALLED AND HOW THE
 LOCATION- SECTION G2419.2 FBC RES.
 G) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX
 CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING
 STANDARDS, AND INSTALLATION GUIDELINES- SECTION
 G2415.1.
  
 2) PLEASE NOTE THE GENERATOR (UNDER SEPARATE PERMIT)
 SHALL BE INSTALLED A MINIMUM OF 5' AWAY FROM
 COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA 37, AND A MINIMUM OF
 10' FROM MECHANICAL OR GRAVITY AIR INTAKES (WINDOW AND
 DOOR OPENINGS) INTO THE BUILDING- SEC. R303.5.1 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  