2020-09-24 11:14:00 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20090781 |
| 9/24/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS ISOMETRIC DRAWING: |
| |
| A) SHOW THE LENGTH, THE TYPE, AND SIZE OF PIPING FROM |
| THE METER TO THE 1-1/2" TEE, FROM THE 1-1/2" TEE TO THE |
| 1-1/4" TEE, AND FROM THE 1-1/4" TEE TO THE PIPE |
| ENTRANCE INTO THE BUILDING. PLEASE CLARIFY IF THE |
| 1-1/4" TEE IS A REDUCER FITTING AND NOT A TEE BECAUSE A |
| SECOND BRANCH LINE IS NOT SHOWN ON THE RISER- SECTIONS |
| G2413.4.1 FBC RES. |
| B) SHOW THE LOCATIONS OF THE LOW PRESSURE REGULATORS |
| FOR THE INTERIOR APPLIANCES AND THE POOL HEATER- |
| SECTION G2421.1 & G2421.2 FBC RES. |
| C) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. THE |
| UPDATED SPECS FOR THE GENERAC 22KW MODEL INDICATE A |
| FULL LOAD OF 306,000 BTUH FOR NATURAL GAS. PLEASE |
| CORRECT THE LOAD SHOWN ON THE RISER. |
| D) THE GENERAC SPECS SHOW A NATURAL GAS INPUT PRESSURE |
| OF 3.5- 7 IN. W.C. HOWEVER THE RISER DRAWING SHOWS A |
| REGULATOR WITH A 11 IN. W.C DELIVERY PRESSURE TO THE |
| GENERATOR. PLEASE CORRECT AND INDICATE THE MAKE AND |
| MODEL OF THE SELECTED REGULATOR ON THE RISER. SUBMIT |
| MARKED UP OR HIGHLIGHTED REGULATOR SPECS SHOWING THE |
| MODEL, INLET AND OUTLET PRESSURES, SPRING SELECTION, |
| AND ORIFICE SIZE- SECTION G2421.1 & G2421.2. SHOW THE |
| REQUIRED PIPE UNIONS AT THE REGULATOR. |
| E) INDICATE HOW THE PE PIPING RISER WILL MAKE |
| CONNECTION TO THE EXISTING PIPING AT THE BBQ- SECTIONS |
| G2415.17.1 & G2415.17.2. PLEASE NOTE THAT SPECS FOR |
| ANODELESS RISERS AND PE/METALLIC PIPE CONNECTORS SHALL |
| BE LISTED AND LABELED. |
| F) INDICATE A DRIP LEG WILL BE INSTALLED AND HOW THE |
| LOCATION- SECTION G2419.2 FBC RES. |
| G) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX |
| CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING |
| STANDARDS, AND INSTALLATION GUIDELINES- SECTION |
| G2415.1. |
| |
| 2) PLEASE NOTE THE GENERATOR (UNDER SEPARATE PERMIT) |
| SHALL BE INSTALLED A MINIMUM OF 5' AWAY FROM |
| COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA 37, AND A MINIMUM OF |
| 10' FROM MECHANICAL OR GRAVITY AIR INTAKES (WINDOW AND |
| DOOR OPENINGS) INTO THE BUILDING- SEC. R303.5.1 FBC |
| RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |