2020-10-06 13:47:42 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20090700 |
| 10/6/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P0.1: THE TYPES AND SIZES OF PIPING MAKING |
| CONNECTIONS FROM THE PE TO THE GWH AND THE RANGE ARE |
| NOT SHOWN- SECTION G2413.1 FBC RES. |
| |
| 2) P0.1, REGULATOR DETAIL: PIPE UNIONS ARE REQUIRED |
| WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR- SECTION |
| G2421.2(7) FBC RES. |
| |
| 3) P0.1: INDICATE A TRACER WIRE WILL BE INSTALLED |
| ADJACENT TO THE UG PE PIPING- SECTION G2415.17.3. |
| |
| 4) SUBMIT SPEC SHEETS FOR THE GENERATOR, WATER HEATER, |
| AND RANGE THAT HAVE BEEN MARKED UP OR HIGHLIGHTED TO |
| INDICATE THE SELECTED MODELS, BTUH CAPACITIES AND INPUT |
| PRESSURES- SECTION G2408.1. PLEASE NOTE THAT |
| INSTALLATION OF THE GENERATOR SHALL BE UNDER SEPARATE |
| PERMIT AND CURRENTLY THERE IS NO APPLICATION AND PLANS |
| SUBMITTED FOR PERMIT ISSUANCE- SECTION 105.1 & 107.2.1 |
| WPB. |
| |
| 5) SUBMIT MARKED UP OR HIGHLIGHTED REGULATOR SPECS |
| SHOWING THE SELECTED MODELS TO BE INSTALLED, INLET AND |
| OUTLET PIPE SIZES AND PRESSURES, SPRING SELECTIONS, AND |
| ORIFICE SIZES- SECTIONS G2421.1 & G2421.2 FBC RES. |
| |
| 6) SHEET PS1.1: SHOW THE GENERATOR CLEARANCE DISTANCES |
| TO THE BUILDINGS, ADJACENT PROPERTY LINES, AND TO |
| MECHANICAL AIR INTAKES AND OPERABLE OPENINGS INTO THE |
| BUILDING- SECTION 4.1.4 NFPA 37, AND SECTION R303.5.1 |
| FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |