Plan Review Notes
Plan Review Notes For Permit 20090696
Permit Number 20090696
Review Stop P
Sequence Number 1
Notes
Date Text
2020-09-18 15:45:051ST REVIEW FBC-2017 RES.
 PERMIT- 20090696
 9/18/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 1: THE SUBMITTED MANUFACTURER'S SPECIFICATIONS
 FOR THE ECOSMART POINT OF USE TANKLESS WATER INDICATE
 THE LARGER ECO 11 HAS A MAX FLOW RATE OF 3.2 GPM AT 77
 DEGREES F. THIS APPEARS TO BE UNDERSIZED TO SUPPLY THE
 BATH FIXTURES AND THE WASHING MACHINE PER THE EXAMPLE
 CALCS IN THE SUBMITTAL, AND ALSO ACCORDING TO TABLE
 P2903.1 FBC RES. PROVIDE ON THE PLAN THE SELECTED MAKE
 AND MODEL NUMBER OF THE WATER HEATER AND A LIST OF
 PLUMBING FIXTURES TO BE SUPPLIED WITH HOT WATER FROM
 THE NEW TANKLESS WATER HEATER. INCLUDE THE REQUIRED
 TOTAL GPM FLOW, AND PROVIDE ADDITIONAL SPECS FROM THE
 MANUFACTURER INCLUDING A TEMPERATURE RISE GRAPH TO
 VERIFY CORRECT SIZING- SECTIONS P2801.4 AND M2005.1 FBC
 RES. PLEASE NOTE THE ECOSMART MANUFACTURER OFFERS
 LARGER MODELS FOR WHOLE HOUSE INSTALLATIONS.
  
 2) SHEET 1: FOR CLARIFICATION PLEASE INDICATE THE
 SHOWER VALVE TO BE A TUB/SHOWER COMBINATION VALVE
 UNLESS A SEPARATE VALVE IS TO BE INSTALLED FOR THE TUB-
 SECTION P2708.4 FBC RES.
  
 3) THE $2000.00 VALUE ON THE APPLICATION APPEARS TO BE
 LOW FOR THE SCOPE OF WORK. PLEASE PROVIDE A COPY OF THE
 CONTRACT AND/OR COPIES OF ESTIMATES AND INVOICE TO
 VERIFY TOTAL COST. PLEASE NOTE THTE TOTAL COST SHALL
 INCLUDE LABOR, MATERIALS, FIXTURES, EQUIPMENT, DESIGN
 FEES, AND OVERHEAD AND PROFIT- SECTION 109.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  