2020-10-08 09:20:44 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20090683 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE ENERGY CALCULATIONS FOR THE NEW AHU |
| IN THE TRAINING ROOM. FBC EC C403.1 |
| |
| 2) PLEASE PROVIDE SCOPE OF TRAINING IN THE TRAINING |
| ROOM. IS THIS AN ASSEMBLY AREA? PLEASE LET THE O.A. |
| CALCULATIONS REFLECT THE USE OF SPACE. FBC M TABLE |
| 403.3.1.1 |
| |
| 3) SHEET M6.1; IN THE OUTDOOR AIR CALCULATIONS CHART |
| THE AHU-1 DOES NOT HAVE A NUMBER IN THE ?PEOPLE OUTDOOR |
| AIR RATE CFM/PERSON, WHY WAS THIS LEFT BLANK? |
| |
| 4) PLEASE SHOW CONDENSATION DISPOSAL FOR AHU-1. FBC M |
| 307.2.1 |
| |
| 5) WHY IS THE DRAWING NOT SHOWING A FD IN THE SUPPLY |
| DUCT AT THE CORRIDOR WALL NEAR THE BATHROOMS BUT IS |
| SHOWING (2) FD?S FOR RETURN AIR IN THE SAME WALL? |
| |
| 6) PLEASE PROVIDE DETAILS FOR THE PRE ENGINEERED STAND |
| FOR THE CONDENSING UNIT. FBC 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |