2021-04-28 07:56:37 | 3RD REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20090652 |
| 4/28/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE RISER SHOWS TWO GAS PIPING OUTLETS AT THE METER |
| HOWEVER METERS TYPICALLY HAVE ONE INLET AND ONE OUTLET. |
| PLEASE REVISE THE RISER TO SHOW THE TYPE AND SIZE OF |
| THE MAIN OUTLET PIPE AND LENGTH OF THE PIPE FROM THE |
| METER TOP THE TEE WHERE THE PE RISER IS CONNECTING. |
| PLEASE NOTE THAT THE PIPE MUST BE SIZED LARGE ENOUGH TO |
| SUPPLY THE INCREASED GAS LOAD OF 875,000 BTUS AT A |
| TOTAL DEVELOPED LENGTH OF 110 FT- SECTION G2413.4.1 FBC |
| RES. |
| |
| A) PLEASE SHOW THE DELIVERY PRESSURE AT THE METER AND |
| PRESSURE DROP FOR THE SYSTEM- G2413.2 & G2413.5. |
| |
| B) LIST ALL PIPE SIZING TABLES ON THE RISER DRAWING- |
| G2413.4. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |