2021-01-14 16:00:46 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20090652 |
| 1/14/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER: BASED ON THE SUBMITTED PE PIPE SIZING |
| TABLE 402.4(21) FBC FG, THE 1-1/4 IN.PE PIPE IS |
| UNDERSIZED TO SUPPLY THE NEW TOTAL LOAD OF 875,000 BTU |
| LOAD AT 110 FT. DEVELOPED LENGTH AS INDICATED ON THE |
| RISER. PLEASE NOTE THE 110 FT. LENGTH DOES NOT APPEAR |
| TO MATCH THE MEASURMENTS ON THE RISER WHICH APPEAR TO |
| INDICATE 80 FT. TOTAL LENGTH.THE 1-1/4 IS ALSO |
| UNDERSIZED TO PROVIDE THE EXISTING LOAD OF 615 BTU |
| BASED ON THE TABLE. |
| |
| 2) GAS RISER: THE NEW 1 IN. PIPE IS LARGE ENOUGH TO |
| SUPPLY THE 260,000 BTU GENERATOR LOAD IF THE NEW PIPE |
| IS DIRECTLY CONNECTED TO THE METER AND NOT TEEING OFF |
| FROM THE EXISTING 1-1/4 IN. PIPE. PLEASE PROVIDE A |
| DETAIL SHOWING THE PIPING CONNECTIONS AT THE METER. |
| COMMENTS 3 & 4 BELOW PERTAIN TO THE EXISTING PIPING |
| WHICH APPEARS TO NOT BE SIZED PROPERLY. |
| |
| 3) GAS RISER: PLEASE PROVIDE THE LENGTH OF THE PE PIPE |
| RUN FROM THE METER TO THE CSST TEE- SECTION G2413.4.1 |
| FBC RES. |
| |
| 4) GAS RISER: BASED ON THE SUBMITTED CSST PIPE SIZING |
| TABLE 402.4(15) THE 1 IN. (31 EHD) IS UNDERSIZED TO |
| SUPPLY THE INTERIOR 270,000 BTU LOAD AT 110 FT. |
| DEVELOPED LENGTH. ACCORDING TO THE TABLE, AN EHD 46 |
| PIPE IS REQUIRED. |
| |
| 5) THE SUBMITTED SURVEY IS APPEARS TO BE A PHOTO IMAGE |
| WITH PRINT TOO SMALL TO READ AND PRINT WHEN ENLARGED |
| FOR REVIEW BECOMES BLURRY AND ILLEGIBLE. PLEASE PROVIDE |
| THE SURVEY IN A FORMAT THAT CAN BE REVIEWED FOR |
| COMPLIANCE- SECTION 107.2.1 WPB. PLEASE MARK THE SURVEY |
| TO SHOW GENERATOR'S LOCATION AND CLEARANCE DISTANCES TO |
| THE BUILDING, ADJACENT PROPERTY LINES, AND AIR INTAKES |
| AND OPERABLE OPENINGS INTO THE BUILDING- SEE SEC. 4.1.4 |
| NFPA 37, AND SEC. R303.5.1 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |