2021-01-14 16:00:462ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090652
 1/14/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER: BASED ON THE SUBMITTED PE PIPE SIZING
 TABLE 402.4(21) FBC FG, THE 1-1/4 IN.PE PIPE IS
 UNDERSIZED TO SUPPLY THE NEW TOTAL LOAD OF 875,000 BTU
 LOAD AT 110 FT. DEVELOPED LENGTH AS INDICATED ON THE
 RISER. PLEASE NOTE THE 110 FT. LENGTH DOES NOT APPEAR
 TO MATCH THE MEASURMENTS ON THE RISER WHICH APPEAR TO
 INDICATE 80 FT. TOTAL LENGTH.THE 1-1/4 IS ALSO
 UNDERSIZED TO PROVIDE THE EXISTING LOAD OF 615 BTU
 BASED ON THE TABLE.
  
 2) GAS RISER: THE NEW 1 IN. PIPE IS LARGE ENOUGH TO
 SUPPLY THE 260,000 BTU GENERATOR LOAD IF THE NEW PIPE
 IS DIRECTLY CONNECTED TO THE METER AND NOT TEEING OFF
 FROM THE EXISTING 1-1/4 IN. PIPE. PLEASE PROVIDE A
 DETAIL SHOWING THE PIPING CONNECTIONS AT THE METER.
 COMMENTS 3 & 4 BELOW PERTAIN TO THE EXISTING PIPING
 WHICH APPEARS TO NOT BE SIZED PROPERLY.
  
 3) GAS RISER: PLEASE PROVIDE THE LENGTH OF THE PE PIPE
 RUN FROM THE METER TO THE CSST TEE- SECTION G2413.4.1
 FBC RES.
  
 4) GAS RISER: BASED ON THE SUBMITTED CSST PIPE SIZING
 TABLE 402.4(15) THE 1 IN. (31 EHD) IS UNDERSIZED TO
 SUPPLY THE INTERIOR 270,000 BTU LOAD AT 110 FT.
 DEVELOPED LENGTH. ACCORDING TO THE TABLE, AN EHD 46
 PIPE IS REQUIRED.
  
 5) THE SUBMITTED SURVEY IS APPEARS TO BE A PHOTO IMAGE
 WITH PRINT TOO SMALL TO READ AND PRINT WHEN ENLARGED
 FOR REVIEW BECOMES BLURRY AND ILLEGIBLE. PLEASE PROVIDE
 THE SURVEY IN A FORMAT THAT CAN BE REVIEWED FOR
 COMPLIANCE- SECTION 107.2.1 WPB. PLEASE MARK THE SURVEY
 TO SHOW GENERATOR'S LOCATION AND CLEARANCE DISTANCES TO
 THE BUILDING, ADJACENT PROPERTY LINES, AND AIR INTAKES
 AND OPERABLE OPENINGS INTO THE BUILDING- SEE SEC. 4.1.4
 NFPA 37, AND SEC. R303.5.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  