2020-10-21 11:42:57 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20090652 |
| 10/21/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER DRAWING: PLEASE PROVIDE A COMPLETE RISER |
| DRAWING THAT INCLUDES THE INTERIOR GAS APPLIANCES |
| INSTALLED UNDER PERMIT 98003449 INCLUDING THE WATER |
| HEATER, DRYER, AND COOKTOP- SECTIONS G2412.3 & G2412.4 |
| FBC RES. |
| |
| A) SHOW THE CORRECT TOTAL LOAD AND THE INDIVIDUAL LOADS |
| OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC |
| RES. PLEASE NOTE THE GENERATOR SPECS INDICATE A FULL |
| LOAD CAPACITY OF 260,000 BTUH FOR NATURAL GAS. |
| |
| B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE |
| PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND |
| THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND |
| G2413.4.2 FBC RES. |
| |
| C) INDICATE THE INPUT GAS PRESSURE FOR THE GENERATOR |
| PER MANUFACTURER'S SPECIFICATIONS AT THE OUTLET SIDE OF |
| THE REGULATOR. PLEASE SUBMIT MARKED UP OR HIGHLIGHTED |
| SPECS FOR THE REGULATOR SHOWING THE SELECTED MODEL, THE |
| MAX INLET AND OUTLET SIZE AND PRESSURES, SPRING DATA, |
| AND ORIFICE SIZE- SECTION G2421. |
| D) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING |
| WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR- SECTION |
| G2421.2(7). |
| |
| 2) PROVIDE A MARKED UP OR HIGHLIGHTED COPY OF THE |
| PROPERTY SURVEY SHOWING THE GENERATOR'S LOCATION AND |
| CLEARANCE DISTANCES TO THE BUILDING, ADJACENT PROPERTY |
| LINES, AND AIR INTAKES AND OPERABLE OPENINGS INTO THE |
| BUILDING- SEE SEC. 4.1.4 NFPA 37, AND SEC. R303.5.1 FBC |
| RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |