Plan Review Notes
Plan Review Notes For Permit 20090652
Permit Number 20090652
Review Stop G
Sequence Number 1
Notes
Date Text
2020-10-21 11:42:571ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090652
 10/21/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING: PLEASE PROVIDE A COMPLETE RISER
 DRAWING THAT INCLUDES THE INTERIOR GAS APPLIANCES
 INSTALLED UNDER PERMIT 98003449 INCLUDING THE WATER
 HEATER, DRYER, AND COOKTOP- SECTIONS G2412.3 & G2412.4
 FBC RES.
  
 A) SHOW THE CORRECT TOTAL LOAD AND THE INDIVIDUAL LOADS
 OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC
 RES. PLEASE NOTE THE GENERATOR SPECS INDICATE A FULL
 LOAD CAPACITY OF 260,000 BTUH FOR NATURAL GAS.
  
 B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE
 PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND
 THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND
 G2413.4.2 FBC RES.
  
 C) INDICATE THE INPUT GAS PRESSURE FOR THE GENERATOR
 PER MANUFACTURER'S SPECIFICATIONS AT THE OUTLET SIDE OF
 THE REGULATOR. PLEASE SUBMIT MARKED UP OR HIGHLIGHTED
 SPECS FOR THE REGULATOR SHOWING THE SELECTED MODEL, THE
 MAX INLET AND OUTLET SIZE AND PRESSURES, SPRING DATA,
 AND ORIFICE SIZE- SECTION G2421.
 D) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING
 WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR- SECTION
 G2421.2(7).
  
 2) PROVIDE A MARKED UP OR HIGHLIGHTED COPY OF THE
 PROPERTY SURVEY SHOWING THE GENERATOR'S LOCATION AND
 CLEARANCE DISTANCES TO THE BUILDING, ADJACENT PROPERTY
 LINES, AND AIR INTAKES AND OPERABLE OPENINGS INTO THE
 BUILDING- SEE SEC. 4.1.4 NFPA 37, AND SEC. R303.5.1 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  