2020-10-27 08:08:27PLAN REVIEW GENERATOR / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PRE-CAST GENERATOR PAD ENGINEERING:
  
 1.GENERATOR PAD ENGINEERING IS BASED ON VULT OF 186MPH
 AND VASD OF 144MPH, RISK CATEGORY III AND EXPOSURE
 CATEGORY D.
  
 PROVIDE GENERATOR PAD DESIGN USING THE EXISTING SITE
 CONDITIONS:
  
 ASSUMED DESIGN CRITERIA FOR THIS SITE: VULT OF 170MPH,
 (FIGURE R301.2(4) ) VASD OF 132MPH (TABLE R301.2.1.3)
 RISK CATEGORY II AND EXPOSURE CATEGORY C.
  
 2.PROPOSED PRE-CAST PAD DEMENSIONS ARE 33.75 X 49
 INCHES.
 GENERATOR DEMENSIONS FROM SPEIFICATIONS PROVIDED ARE
 29.6 X 48.1 INCHES.
 ANCHORS REQUIRE A MINIMUM OF 3 INCH EDGE DISTANCE.
 IT APPEARS THE PROPOSED PAD IS TOO SMALL.
  
 3.PROVIDE LOCATION OF GENERATOR ON SURVEY. PROVIDE
 DEMENSIONS TO PROPERTY LINES, TO STRUCTURE AND TO
 OPENINGS IN STRUCTURE.
  
 R303.5.1 INTAKE OPENINGS: MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  