Plan Review Notes
Plan Review Notes For Permit 20090644
Permit Number 20090644
Review Stop E
Sequence Number 4
Notes
Date Text
2021-05-21 13:36:18CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: FAILED.
  
 1) SHEET E-1.0: RECEPTACLES ON NEW WALLS ARE SHOWN AS
 EXISTING. PLEASE CORRECT TO PROPERLY DESIGNATE NEW
 RECEPTACLES AND EXISTING ONES.
 2) SHEET E-2.0: ALL LIGHTING FIXTURES ARE SHOWN AS
 EXISTING WITH NONE TO BE RELOCATED OR NEW. PLEASE
 CONFIRM THIS IS THE CASE.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ PE
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  