Plan Review Notes
Plan Review Notes For Permit 20090644
Permit Number 20090644
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2021-05-03 14:13:51FIRE PROVISO
  
 THERE ARE INDICATION OF SLIDING DOOR ASSEMBLIES IN TWO
 CLASSROOMS.
  
 THEY SHALL MEETING THE FOLLOWING EGRESS REQQUIRMENTS
 WHERE APPLICABLE.
  
 (4) HORIZONTAL-SLIDING DOOR ASSEMBLIES SHALL BE
 PERMITTED UNDER ANY
 OF THE FOLLOWING CONDITIONS:
 (A) HORIZONTAL-SLIDING DOOR ASSEMBLIES IN DETENTION AND
 CORRECTIONAL
 OCCUPANCIES, AS PROVIDED IN CHAPTERS 22 AND 23, SHALL
 BE PERMITTED.
 (B) SPECIAL-PURPOSE HORIZONTALLY SLIDING ACCORDION OR
 FOLDING DOOR
 ASSEMBLIES COMPLYING WITH 7.2.1.14 SHALL BE PERMITTED.
 (C) UNLESS PROHIBITED BY CHAPTERS 11 THROUGH 43,
 HORIZONTALSLIDING
 DOOR ASSEMBLIES SERVING A ROOM OR AREA WITH AN OCCUPANT
 LOAD OF FEWER THAN 10 SHALL BE PERMITTED, PROVIDED THAT
 ALL OF THE FOLLOWING CRITERIA ARE MET:
 I. THE AREA SERVED BY THE DOOR ASSEMBLY HAS NO HIGH
 HAZARD
 CONTENTS.
 II. THE DOOR ASSEMBLY IS READILY OPERABLE FROM EITHER
 SIDE
 WITHOUT SPECIAL KNOWLEDGE OR EFFORT.
 III. THE FORCE REQUIRED TO OPERATE THE DOOR ASSEMBLY IN
 THE
 DIRECTION OF DOOR LEAF TRAVEL IS NOT MORE THAN 30 LBF
 (133 N)
 TO SET THE DOOR LEAF IN MOTION AND IS NOT MORE THAN 15
 LBF
 (67 N) TO CLOSE THE DOOR ASSEMBLY OR OPEN IT TO THE
 MINIMUM
 REQUIRED WIDTH.
 IV. THE DOOR ASSEMBLY COMPLIES WITH ANY REQUIRED FIRE
 PROTECTION
 RATING, AND, WHERE RATED, IS SELF-CLOSING OR
 AUTOMATICCLOSING
 BY MEANS OF SMOKE DETECTION IN ACCORDANCE WITH
 7.2.1.8 AND IS INSTALLED IN ACCORDANCE WITH NFPA 80.
 V. CORRIDOR DOOR ASSEMBLIES REQUIRED TO BE
 SELF-LATCHING HAVE
 A LATCH OR OTHER MECHANISM THAT ENSURES THAT THE DOOR
 LEAF
 WILL NOT REBOUND INTO A PARTIALLY OPEN POSITION IF
 FORCEFULLY
 CLOSED.
 (D) WHERE PRIVATE GARAGES, BUSINESS AREAS, INDUSTRIAL
 AREAS, AND
 STORAGE AREAS WITH AN OCCUPANT LOAD NOT EXCEEDING 10
 CONTAIN
 ONLY LOW OR ORDINARY HAZARD CONTENTS, DOOR OPENINGS TO
 SUCH
 AREAS AND PRIVATE GARAGES SHALL BE PERMITTED TO BE
 HORIZONTALSLIDING
 DOOR ASSEMBLIES.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE.
  
 THE FIRE INSPECTOR WILL CONFIRM COMPLIANCE ON
 INSPECTION.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  