2021-05-03 14:13:51 | FIRE PROVISO |
| |
| THERE ARE INDICATION OF SLIDING DOOR ASSEMBLIES IN TWO |
| CLASSROOMS. |
| |
| THEY SHALL MEETING THE FOLLOWING EGRESS REQQUIRMENTS |
| WHERE APPLICABLE. |
| |
| (4) HORIZONTAL-SLIDING DOOR ASSEMBLIES SHALL BE |
| PERMITTED UNDER ANY |
| OF THE FOLLOWING CONDITIONS: |
| (A) HORIZONTAL-SLIDING DOOR ASSEMBLIES IN DETENTION AND |
| CORRECTIONAL |
| OCCUPANCIES, AS PROVIDED IN CHAPTERS 22 AND 23, SHALL |
| BE PERMITTED. |
| (B) SPECIAL-PURPOSE HORIZONTALLY SLIDING ACCORDION OR |
| FOLDING DOOR |
| ASSEMBLIES COMPLYING WITH 7.2.1.14 SHALL BE PERMITTED. |
| (C) UNLESS PROHIBITED BY CHAPTERS 11 THROUGH 43, |
| HORIZONTALSLIDING |
| DOOR ASSEMBLIES SERVING A ROOM OR AREA WITH AN OCCUPANT |
| LOAD OF FEWER THAN 10 SHALL BE PERMITTED, PROVIDED THAT |
| ALL OF THE FOLLOWING CRITERIA ARE MET: |
| I. THE AREA SERVED BY THE DOOR ASSEMBLY HAS NO HIGH |
| HAZARD |
| CONTENTS. |
| II. THE DOOR ASSEMBLY IS READILY OPERABLE FROM EITHER |
| SIDE |
| WITHOUT SPECIAL KNOWLEDGE OR EFFORT. |
| III. THE FORCE REQUIRED TO OPERATE THE DOOR ASSEMBLY IN |
| THE |
| DIRECTION OF DOOR LEAF TRAVEL IS NOT MORE THAN 30 LBF |
| (133 N) |
| TO SET THE DOOR LEAF IN MOTION AND IS NOT MORE THAN 15 |
| LBF |
| (67 N) TO CLOSE THE DOOR ASSEMBLY OR OPEN IT TO THE |
| MINIMUM |
| REQUIRED WIDTH. |
| IV. THE DOOR ASSEMBLY COMPLIES WITH ANY REQUIRED FIRE |
| PROTECTION |
| RATING, AND, WHERE RATED, IS SELF-CLOSING OR |
| AUTOMATICCLOSING |
| BY MEANS OF SMOKE DETECTION IN ACCORDANCE WITH |
| 7.2.1.8 AND IS INSTALLED IN ACCORDANCE WITH NFPA 80. |
| V. CORRIDOR DOOR ASSEMBLIES REQUIRED TO BE |
| SELF-LATCHING HAVE |
| A LATCH OR OTHER MECHANISM THAT ENSURES THAT THE DOOR |
| LEAF |
| WILL NOT REBOUND INTO A PARTIALLY OPEN POSITION IF |
| FORCEFULLY |
| CLOSED. |
| (D) WHERE PRIVATE GARAGES, BUSINESS AREAS, INDUSTRIAL |
| AREAS, AND |
| STORAGE AREAS WITH AN OCCUPANT LOAD NOT EXCEEDING 10 |
| CONTAIN |
| ONLY LOW OR ORDINARY HAZARD CONTENTS, DOOR OPENINGS TO |
| SUCH |
| AREAS AND PRIVATE GARAGES SHALL BE PERMITTED TO BE |
| HORIZONTALSLIDING |
| DOOR ASSEMBLIES. |
| |
| PLEASE REVIEW AND ENSURE COMPLIANCE. |
| |
| THE FIRE INSPECTOR WILL CONFIRM COMPLIANCE ON |
| INSPECTION. |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |