2020-11-06 10:49:13 | CODES IN EFFECT |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: FAILED. |
| |
| SAME COMMENTS AS PRIOR REVIEW. SEE BELOW: |
| |
| 1) NO ELECTRIC IS SHOWN. NOT ENOUGH INFORMATION TO MAKE |
| A GOOD REVIEW OF THE FACILITY. |
| |
| 2) OUTLETS IN A DAY CARE OCCUPANCY SHALL BE TAMPER |
| RESISTANT TYPE PER 406.12(C) |
| |
| 3) 406.12 TAMPER-RESISTANT RECEPTACLES TAMPER-RESISTANT |
| RECEPTACLES SHALL BE INSTALLED AS SPECIFIED IN |
| 406.12(A) THROUGH (C). |
| 4) (C) CHILD CARE FACILITIES. IN ALL CHILD CARE |
| FACILITIES, ALL NONLOCKING-TYPE 125-VOLT, 15- AND |
| 20-AMPERE RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT |
| RECEPTACLES. |
| |
| 406.2 DEFINITION CHILD CARE FACILITY. A BUILDING OR |
| STRUCTURE, OR PORTION THEREOF, FOR EDUCATIONAL, |
| SUPERVISORY, OR PERSONAL CARE SERVICES FOR MORE THAN |
| FOUR CHILDREN 7 YEARS OLD OR LESS. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |