Plan Review Notes For Permit 20090644 |
Permit Number |
20090644 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2021-05-07 15:15:27 | CHANGE OF OCCUPANCY CLASSIFICATION FROM (B) TO(E) | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | 2017 FBC EXISTING BUILDING - CHANGE OF OCCUPANCY | | CLASSIFICATION | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE SHOW THE TOILET REAR GRAB BAR CENTERLINE | | DIMENSIONS PER FBC ACCESSIBILITY FIGURE 604.5.2 TO | | AVOID INCORRECT INSTALLATION. | | 2) PLEASE SHOW THE GRAB BAR MAXIMUM HEIGHT TO THE TOP | | OF THE GRIPPING SURFACE NOT THE CENTER OF THE BAR PER | | FBC ACCESSIBILITY 609.4 | | 3) THERE IS A NOTE ON DRAWING A 3.0 FROM THE FIRE PLAN | | REVIEWER STATING THAT THE ADDED SLIDING GLASS DOORS | | NEED TO BE ABLE TO SWING OUT - THE PRODUCT APPROVAL FOR | | THE SLIDING GLASS DOOR DOES NOT SHOW THE OPTION TO | | SWING OUT. | | |
|