2020-09-17 16:27:33ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC IS SHOWN. NOT ENOUGH INFORMATION TO MAKE A
 GOOD REVIEW OF THE FACILITY.
  
 OUTLETS IN A DAY CARE OCCUPANCY SHALL BE TAMPER
 RESISTANT TYPE PER 406.12(C)
  
 406.12 TAMPER-RESISTANT RECEPTACLES TAMPER-RESISTANT
 RECEPTACLES SHALL BE INSTALLED AS SPECIFIED IN
 406.12(A) TH ROUGH (C).
 (C) CHILD CARE FACILITIES. IN ALL CHILD CARE
 FACILITIES, ALL NONLOCKING-TYPE 125-VOLT, 15- AND
 20-AMPERE RECEPTAC LES SHALL BE LISTED TAMPER-RESISTANT
 RECEPTACLES.
  
 406.2 DEFINITION CHILD CARE FACILITY. A BUILDING OR
 STRUCTURE, OR PORTION THEREOF, FOR EDUCATIONAL,
 SUPERVISORY, OR PERSONAL CARE SERVICES FOR MORE THAN
 FOUR CHILDREN 7 YEARS OLD OR LESS.
  
  