Plan Review Notes For Permit 20090644 |
Permit Number |
20090644 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-09-17 16:27:33 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | NO ELECTRIC IS SHOWN. NOT ENOUGH INFORMATION TO MAKE A | | GOOD REVIEW OF THE FACILITY. | | | | OUTLETS IN A DAY CARE OCCUPANCY SHALL BE TAMPER | | RESISTANT TYPE PER 406.12(C) | | | | 406.12 TAMPER-RESISTANT RECEPTACLES TAMPER-RESISTANT | | RECEPTACLES SHALL BE INSTALLED AS SPECIFIED IN | | 406.12(A) TH ROUGH (C). | | (C) CHILD CARE FACILITIES. IN ALL CHILD CARE | | FACILITIES, ALL NONLOCKING-TYPE 125-VOLT, 15- AND | | 20-AMPERE RECEPTAC LES SHALL BE LISTED TAMPER-RESISTANT | | RECEPTACLES. | | | | 406.2 DEFINITION CHILD CARE FACILITY. A BUILDING OR | | STRUCTURE, OR PORTION THEREOF, FOR EDUCATIONAL, | | SUPERVISORY, OR PERSONAL CARE SERVICES FOR MORE THAN | | FOUR CHILDREN 7 YEARS OLD OR LESS. | | | | |
|