2020-11-06 13:48:02CHANGE OF OCCUPANCY CLASSIFICATION FROM (B) TO(E)
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
 2017 FBC EXISTING BUILDING - CHANGE OF OCCUPANCY
 CLASSIFICATION
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) OCCUPANT LOAD SHOULD BE DETERMINED BY ROOM USE PER
 FBC 1004 - SHOW THE USE AND THE OCCUPANT LOAD FOR EACH
 ROOM.
 2) PLEASE SHOW ALL DOOR WIDTHS - FBC 1010.1.1
 3) PLEASE SHOW THAT DOORS THAT SWING INTO THE CORRIDOR
 COMPLY WITH - 1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
 4) PLEASE SHOW THE GLAZING IN THE FIRE RATED CORRIDOR
 WALLS COMPLIES WITH FBC 716.2
 5) PLEASE SHOW THE FIRE RATING, SELF LATCHING AND SELF
 CLOSING OF THE CORRIDOR DOORS TO COMPLY WITH FBC 716
 6) EGRESS DOOR IN THE "MULTIPURPOSE ROOM" LEADING TO
 THE EGRESS CORRIDOR NEEDS TO COMPLY WITH FBC 1010.1.2.1
 DIRECTION OF SWING.
 PIVOT OR SIDE-HINGED SWINGING DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA
 CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS
 (ASSEMBLY AT 7SQ.FT. PER PERSON = 244 OCCUPANTS) -
 PLEASE PROVIDE AN EXIT SIGN AT THIS LOCATION ALSO.
 7) PLEASE SHOW THE CORRIDOR WALL FIRE RATING TO COMPLY
 WITH FBC 466.8 (FBC 708.4 CONTINUITY. FIRE PARTITIONS
 SHALL EXTEND FROM THE TOP OF THE FOUNDATION OR
 FLOOR/CEILING ASSEMBLY BELOW TO THE UNDERSIDE OF THE
 FLOOR OR ROOF SHEATHING, SLAB OR DECK ABOVE OR TO THE
 FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING
 ASSEMBLY ABOVE, AND SHALL BE SECURELY ATTACHED
 THERETO.)
 8) PLEASE SHOW FIRE ALARMS TO COMPLY WITH - FBC 466.7
 -- SHOW LOCATION OF SMOKE DETECTORS TO COMPLY WITH
 466.7.2DETECTION.
 A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN
 EACH STORY IN FRONT OF DOORS TO THE STAIRWAYS AND IN
 THE CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAY CARE
 OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN
 LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY
 CARE OCCUPANCY.
 9) PLEASE STATE ON THE SITE PLAN THAT THE PARKING LOT
 AND EXTERIOR PLAY AREA WILL BE ON A SEPARATE PERMIT.
 10) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON
 RESPONSIBLE FOR THE DESIGN. FBC WPB AMENDMENTS 107.2.1
 11) PLEASE MARK ALL ARCHITECTURAL DRAWINGS BY STEVE
 SIEBERT FOR REFERENCE ONLY - OR PROVIDE ORIGINAL SIGNED
 AND SEALED DRAWINGS FROM ARCHITECT STEVE SIEBERT
 WITHOUT THE CITY STAMP ON THEM.
 12) SHOW NEW RESTROOM TO MEET ACCESSIBILITY
 REQUIREMENTS FBC ACCESSIBILITY 213.2
 13) SHOW ALL REQUIRED EXIT SIGNS TO COMPLY WITH FBC
 1013.1
 14) SHOW EXIT EMERGENCY LIGHTING TO COMPLY WITH FBC
 1008.3
  