2020-11-06 13:48:02 | CHANGE OF OCCUPANCY CLASSIFICATION FROM (B) TO(E) |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| 2017 FBC EXISTING BUILDING - CHANGE OF OCCUPANCY |
| CLASSIFICATION |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) OCCUPANT LOAD SHOULD BE DETERMINED BY ROOM USE PER |
| FBC 1004 - SHOW THE USE AND THE OCCUPANT LOAD FOR EACH |
| ROOM. |
| 2) PLEASE SHOW ALL DOOR WIDTHS - FBC 1010.1.1 |
| 3) PLEASE SHOW THAT DOORS THAT SWING INTO THE CORRIDOR |
| COMPLY WITH - 1005.7.1 DOORS. |
| DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED |
| WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY |
| POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE |
| THAN ONE-HALF. |
| 4) PLEASE SHOW THE GLAZING IN THE FIRE RATED CORRIDOR |
| WALLS COMPLIES WITH FBC 716.2 |
| 5) PLEASE SHOW THE FIRE RATING, SELF LATCHING AND SELF |
| CLOSING OF THE CORRIDOR DOORS TO COMPLY WITH FBC 716 |
| 6) EGRESS DOOR IN THE "MULTIPURPOSE ROOM" LEADING TO |
| THE EGRESS CORRIDOR NEEDS TO COMPLY WITH FBC 1010.1.2.1 |
| DIRECTION OF SWING. |
| PIVOT OR SIDE-HINGED SWINGING DOORS SHALL SWING IN THE |
| DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA |
| CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS |
| (ASSEMBLY AT 7SQ.FT. PER PERSON = 244 OCCUPANTS) - |
| PLEASE PROVIDE AN EXIT SIGN AT THIS LOCATION ALSO. |
| 7) PLEASE SHOW THE CORRIDOR WALL FIRE RATING TO COMPLY |
| WITH FBC 466.8 (FBC 708.4 CONTINUITY. FIRE PARTITIONS |
| SHALL EXTEND FROM THE TOP OF THE FOUNDATION OR |
| FLOOR/CEILING ASSEMBLY BELOW TO THE UNDERSIDE OF THE |
| FLOOR OR ROOF SHEATHING, SLAB OR DECK ABOVE OR TO THE |
| FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING |
| ASSEMBLY ABOVE, AND SHALL BE SECURELY ATTACHED |
| THERETO.) |
| 8) PLEASE SHOW FIRE ALARMS TO COMPLY WITH - FBC 466.7 |
| -- SHOW LOCATION OF SMOKE DETECTORS TO COMPLY WITH |
| 466.7.2DETECTION. |
| A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN |
| ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN |
| EACH STORY IN FRONT OF DOORS TO THE STAIRWAYS AND IN |
| THE CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAY CARE |
| OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN |
| LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY |
| CARE OCCUPANCY. |
| 9) PLEASE STATE ON THE SITE PLAN THAT THE PARKING LOT |
| AND EXTERIOR PLAY AREA WILL BE ON A SEPARATE PERMIT. |
| 10) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON |
| RESPONSIBLE FOR THE DESIGN. FBC WPB AMENDMENTS 107.2.1 |
| 11) PLEASE MARK ALL ARCHITECTURAL DRAWINGS BY STEVE |
| SIEBERT FOR REFERENCE ONLY - OR PROVIDE ORIGINAL SIGNED |
| AND SEALED DRAWINGS FROM ARCHITECT STEVE SIEBERT |
| WITHOUT THE CITY STAMP ON THEM. |
| 12) SHOW NEW RESTROOM TO MEET ACCESSIBILITY |
| REQUIREMENTS FBC ACCESSIBILITY 213.2 |
| 13) SHOW ALL REQUIRED EXIT SIGNS TO COMPLY WITH FBC |
| 1013.1 |
| 14) SHOW EXIT EMERGENCY LIGHTING TO COMPLY WITH FBC |
| 1008.3 |
| |