2020-09-17 16:18:06 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE IS INSUFFICIENT INFOORMATION PROVIDED TO |
| CONDUCT A DETAILED LIFE SAFETY REVIEW. |
| |
| A CHILDCARE/DAYCARE OCCUPANCY SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE 6TH ED. OF THE FLORIDA FIRE |
| PREVENTION CODE INCLUDING NFPA 101 AND NFPA 1; 2015 ED. |
| |
| 16.1 GENERAL REQUIREMENTS. |
| 16.1.1* APPLICATION. |
| 16.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY |
| TO NEW |
| BUILDINGS OR PORTIONS THEREOF USED AS DAY-CARE |
| OCCUPANCIES. (SEE |
| 1.3.1.) |
| |
| 16.1.1.4 THE REQUIREMENTS OF SECTIONS 16.1 THROUGH 16.5 |
| AND |
| SECTION 16.7 SHALL APPLY TO DAY-CARE OCCUPANCIES IN |
| WHICH MORE |
| THAN 12 CLIENTS RECEIVE CARE, MAINTENANCE, AND |
| SUPERVISION BY |
| OTHER THAN THEIR RELATIVE(S) OR LEGAL GUARDIAN(S) FOR |
| LESS THAN 24 |
| HOURS PER DAY. |
| |
| 16.1.1.6 WHERE A FACILITY HOUSES MORE THAN ONE AGE |
| GROUP OR SELFPRESERVATION |
| CAPABILITY, THE STRICTEST REQUIREMENTS APPLICABLE TO |
| ANY GROUP PRESENT SHALL APPLY THROUGHOUT THE DAY-CARE |
| OCCUPANCY |
| OR BUILDING, AS APPROPRIATE TO A GIVEN AREA, UNLESS THE |
| AREA HOUSING |
| SUCH A GROUP IS MAINTAINED AS A SEPARATE FIRE AREA. |
| |
| PLEASE PROVIDE DETAILS |
| |
| |
| |
| |
| 2) THE APPLICATION INDICATES AN OCCUPANCY CHANGE FROM |
| BUSINESS TO CHILDCARE |
| |
| THERE APPEARS TO BE A BAND, DANCE AND OTHER PRIVATE |
| LESSON ROOMS AND A PRE-SCHOOLD ROOM. |
| |
| |
| 16.1.2 CLASSIFICATION OF OCCUPANCY. SEE 6.1.4. |
| 16.1.2.1 GENERAL. OCCUPANCIES THAT INCLUDE PRESCHOOLS, |
| KINDERGARTENS, AND OTHER SCHOOLS WHOSE PURPOSE IS |
| PRIMARILY |
| EDUCATIONAL FOR CHILDREN 24 MONTHS OF AGE OR OLDER, |
| EVEN THOUGH |
| THE CHILDREN WHO ATTEND SUCH SCHOOLS ARE OF PRESCHOOL |
| AGE, SHALL |
| COMPLY WITH THE PROVISIONS OF CHAPTER 14. |
| |
| |
| PLEASE PROVIDE A DETAILED NARRATIVE OF THE NATURE OF |
| THE CARE, PROPOSED AGES, |
| |
| |
| |
| |
| 3) THERE ARE NO INDICATIONS OF FIRE SPRINKLER AND/OR |
| FIRE ALARM SYSTEMS. |
| |
| PER NFPA 101 |
| |
| 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN |
| DAY-CARE |
| OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR |
| OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN |
| EXTERIOR |
| EXIT ACCESS BALCONY IN ACCORDANCE WITH 7.5.3, SHALL BE |
| PROVIDED |
| WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION |
| 9.6. |
| |
| 16.3.4.5 DETECTION. A SMOKE DETECTION SYSTEM IN |
| ACCORDANCE |
| WITH SECTION 9.6 SHALL BE INSTALLED IN DAY-CARE |
| OCCUPANCIES, OTHER |
| THAN THOSE HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR |
| OPENING |
| DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN |
| EXTERIOR EXIT ACCESS |
| BALCONY IN ACCORDANCE WITH 7.5.3, AND SUCH SYSTEM SHALL |
| COMPLY |
| WITH BOTH OF THE FOLLOWING: |
| (1) DETECTORS SHALL BE INSTALLED ON EACH STORY IN FRONT |
| OF THE DOORS |
| TO THE STAIRWAYS AND IN THE CORRIDORS OF ALL FLOORS |
| OCCUPIED BY |
| THE DAY-CARE OCCUPANCY. |
| (2) DETECTORS SHALL BE INSTALLED IN LOUNGES, RECREATION |
| AREAS, AND |
| SLEEPING ROOMS IN THE DAY-CARE OCCUPANCY. |
| |
| 16.3.5 EXTINGUISHMENT REQUIREMENTS. |
| 16.3.5.1 ANY REQUIRED SPRINKLER SYSTEMS SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 9.7. |
| 16.3.5.2 REQUIRED SPRINKLER SYSTEMS SHALL BE INSTALLED |
| IN ACCORDANCE |
| WITH 9.7.1.1(1). |
| |
| PLEASE REVIEW AND PROVIDE DETAILS. |
| |
| |
| |
| 4) THERE IS AN INDICATION OF SEVERAL CORRIDORS. |
| |
| 16.3.6 CORRIDORS. EVERY INTERIOR CORRIDOR SHALL BE |
| CONSTRUCTED OF |
| WALLS HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE |
| RATING IN |
| ACCORDANCE WITH SECTION 8.3, UNLESS OTHERWISE PERMITTED |
| BY ANY OF |
| THE FOLLOWING: |
| (1) CORRIDOR PROTECTION SHALL NOT BE REQUIRED WHERE ALL |
| SPACES |
| NORMALLY SUBJECT TO CLIENT OCCUPANCY HAVE NOT LESS THAN |
| ONE |
| DOOR OPENING DIRECTLY TO THE OUTSIDE OR TO AN EXTERIOR |
| EXIT |
| ACCESS BALCONY OR CORRIDOR IN ACCORDANCE WITH 7.5.3. |
| (2) IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| SUPERVISED |
| AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| 9.7, |
| CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE RATED, |
| PROVIDED THAT |
| SUCH WALLS FORM SMOKE PARTITIONS IN ACCORDANCE WITH |
| SECTION |
| 8.4. |
| (3) WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A |
| 1-HOUR FIRE |
| RESISTANCE RATING WHERE TESTED AS A WALL, THE CORRIDOR |
| WALLS |
| SHALL BE PERMITTED TO TERMINATE AT THE CORRIDOR |
| CEILING. |
| (4) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED |
| FROM CORRIDORS, |
| PROVIDED THAT THEY ARE SEPARATED FROM ALL OTHER SPACES |
| BY WALLS |
| HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE RATING IN |
| ACCORDANCE WITH SECTION 8.3. |
| (5) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED |
| FROM CORRIDORS, |
| PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA ARE MET: |
| (A) THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| APPROVED, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| WITH |
| SECTION 9.7. |
| (B) THE WALLS SEPARATING THE LAVATORY FROM OTHER ROOMS |
| FORM |
| SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 8.4. |
| WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION |
| CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL |
| OF THE ABOVE. |
| |
| PLEASE REIVEW AND PROVIDE DETAILS |
| |
| |
| |
| 5) THERE ARE SERVAL EXIT DOORS BUT NO OCCUPANCY LOAD |
| CALCULATION. |
| |
| 16.2.2.2.2 PANIC HARDWARE OR FIRE EXIT HARDWARE. ANY |
| DOOR IN A |
| REQUIRED MEANS OF EGRESS FROM AN AREA HAVING AN |
| OCCUPANT LOAD OF |
| 100 OR MORE PERSONS SHALL BE PERMITTED TO BE PROVIDED |
| WITH A LATCH |
| OR LOCK ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR |
| FIRE EXIT |
| HARDWARE COMPLYING WITH 7.2.1.7. |
| |
| 16.2.2.2.4* DOOR LATCHES. EVERY DOOR LATCH TO CLOSETS, |
| STORAGE |
| AREAS, KITCHENS, AND OTHER SIMILAR SPACES OR AREAS |
| SHALL BE SUCH |
| THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE SPACE OR |
| AREA. |
| 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK |
| SHALL BE |
| DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR FROM THE |
| OUTSIDE |
| BY AN OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE |
| TO THE STAFF. |
| |
| PLEASE REIVEW AND PROVIDE DETAILS |
| |
| |
| |
| 6) THERE ARE WINDOWS INDICATED BUT NO DETAILES. |
| |
| 16.2.11.1 WINDOWS FOR RESCUE. |
| 16.2.11.1.1 EVERY ROOM OR SPACE NORMALLY SUBJECT TO |
| CLIENT |
| OCCUPANCY, OTHER THAN BATHROOMS, SHALL HAVE NOT LESS |
| THAN ONE |
| OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH |
| ALL OF THE |
| FOLLOWING, UNLESS OTHERWISE PERMITTED BY 16.2.11.1.2: |
| (1) SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE |
| WITHOUT THE |
| USE OF TOOLS AND SHALL PROVIDE A CLEAR OPENING OF NOT |
| LESS THAN |
| 20 IN. (510 MM) IN WIDTH, 24 IN. (610 MM) IN HEIGHT, |
| AND 5.7 |
| FT2 (0.5 M2) IN AREA. |
| (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44 |
| IN. (1120 |
| MM) ABOVE THE FLOOR. |
| (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID, |
| WITH A WIDTH |
| AND HEIGHT THAT PROVIDES NOT LESS THAN THE REQUIRED 5.7 |
| FT2 (0.5 |
| M2) OPENING AND A DEPTH OF NOT LESS THAN 20 IN. (510 |
| MM), TO |
| PASS FULLY THROUGH THE OPENING. |
| 16.2.11.1.2 THE REQUIREMENTS OF 16.2.11.1.1 SHALL NOT |
| APPLY TO |
| EITHER OF THE FOLLOWING: |
| (1) BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| SUPERVISED |
| AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| 9.7 |
| (2) WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY |
| TO AN EXIT |
| OR DIRECTLY TO THE OUTSIDE OF THE BUILDING |
| |
| PLEASE REIVEW AND PROVIDE DETAILS |
| |
| |
| 7) THERE ARE TWO DOORS THAT APPEAR TO OPEN OUT INTO THE |
| REQUIRED EGRESS PATH. |
| |
| ONE DOOR IS INDICATED IN THE REAR CORRIDOR OPPISTE THE |
| STAFF RESTROOM. |
| |
| THE OTHER IS LOCATED FROM THE FRONT CORRIDOR INTO THE |
| LOBBY. |
| |
| PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| |
| 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| EXISTING BUILDING. |
| (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| WIDTH OF THE STAIR LANDING WHEN THE DOOR |
| LEAF IS FULLY OPEN. |
| |
| PLEASE REIVEW AND CORRECT |
| |
| |
| |
| 8) THERE IS AN INDICATION OF A KITCHEN WITH A STOVE |
| TOP. |
| |
| 16.3.2.3 COOKING FACILITIES SHALL BE PROTECTED IN |
| ACCORDANCE WITH |
| 9.2.3, UNLESS OTHERWISE PERMITTED BY 16.3.2.4 OR |
| 16.3.2.5. |
| |
| 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY |
| ANOTHER |
| SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS |
| SHALL BE PROTECTED |
| IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION |
| CONTROL AND |
| FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS, |
| UNLESS SUCH |
| INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, |
| WHICH SHALL BE |
| PERMITTED TO BE CONTINUED IN SERVICE. |
| |
| 16.3.2.4 OPENINGS SHALL NOT BE REQUIRED TO BE PROTECTED |
| BETWEEN |
| FOOD PREPARATION AREAS AND DINING AREAS. |
| |
| 16.3.2.5 APPROVED DOMESTIC COOKING EQUIPMENT USED FOR |
| FOOD |
| WARMING OR LIMITED COOKING SHALL NOT BE REQUIRED TO BE |
| PROTECTED. |
| |
| PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT PER 9.2.3 |
| |
| |
| |
| 9) THERE IS NO LIFE SAFETY PLAN |
| |
| 4.6.9 CONDITIONS FOR OCCUPANCY. |
| 4.6.9.1 NO NEW CONSTRUCTION OR EXISTING BUILDING SHALL |
| BE |
| OCCUPIED IN WHOLE OR IN PART IN VIOLATION OF THE |
| PROVISIONS OF THIS |
| CODE, UNLESS THE FOLLOWING CONDITIONS EXIST: |
| (1) A PLAN OF CORRECTION HAS BEEN APPROVED. |
| (2) THE OCCUPANCY CLASSIFICATION REMAINS THE SAME. |
| (3) NO SERIOUS LIFE SAFETY HAZARD EXISTS AS JUDGED BY |
| THE |
| AUTHORITY HAVING JURISDICTION. |
| |
| PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN |
| |
| |
| |
| 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |