Plan Review Notes
Plan Review Notes For Permit 20090641
Permit Number 20090641
Review Stop G
Sequence Number 2
Notes
Date Text
2021-02-11 09:01:112ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090641
 2/11/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 NFPA 58- 2014
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW PRINTED BELOW WERE NOT
 ADDRESSED. NO CORRECTIONS WERE MADE TO THE GAS PLAN.
  
 1) SHOW THE SEPARATION DISTANCE BETWEEN THE TWO
 UNDERGROUND TANKS. A 3 FT. SEPARATION IS REQUIRED PER
 TABLE 6.3.1.1 NFPA 58-14.
  
 2) REVISE THE RISER DRAWING TO SHOW THE TANKS
 MANIFOLDED TOGETHER, AND PROVIDE A DETAIL SHOWING HOW
 THE PIPING INTERCONNECTION WILL BE MADE- SECTION
 6.9.3.9 NFPA 58. PLEASE NOTE THAT PE PIPE CANNOT BE
 USED FOR PERMANENT INTERCONNECTION OF THE TANKS-
 SECTION 6.9.3.9B NFPA 58.
  
 3) SHOW HOW THE REGULATOR WILL BE CONNECTED TO THE
 MANIFOLD- SECTION 6.8.1.1 NFPA 58.
  
 NEW COMMENT:
 1) I WAS UNABLE TO FIND A PERMIT ON FILE FOR THE
 EXISTING TANK THAT WAS DESIGNATED TO BE REPLACED AND IS
 NOW TO BE LEFT IN PLACE ACCORDING TO THE REVISED PLAN.
 THE TANK SHALL BE REVIEWED AS A NEW INSTALLATION.
 PLEASE INDICATE THE GALLON SIZE OF THE TANK ON THE
 PLANS AND SUBMIT MANUFACTURER'S SPECIFICATIONS IN
 ACCORDANCE WITH SECTION 5.2.1.1 NFPA 58. THE SPECS FOR
 THE TANK, CATHODIC PROTECTION SYSTEM, AND TANK
 HOLD-DOWN DETAILS SUBMITTED UNDER THE MASTER PERMIT CAN
 BE USED IF THOSE SPECS ARE APPLICABLE TO THE EXISTING
 TANK- SECTIONS 6.6.1.6, 6.6.6.1 NFPA 58. PLEASE PROVIDE
 NOTES ON THE PLAN TO CLARIFY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  