2021-02-11 09:01:11 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20090641 |
| 2/11/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| NFPA 58- 2014 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| COMMENTS FROM THE 1ST REVIEW PRINTED BELOW WERE NOT |
| ADDRESSED. NO CORRECTIONS WERE MADE TO THE GAS PLAN. |
| |
| 1) SHOW THE SEPARATION DISTANCE BETWEEN THE TWO |
| UNDERGROUND TANKS. A 3 FT. SEPARATION IS REQUIRED PER |
| TABLE 6.3.1.1 NFPA 58-14. |
| |
| 2) REVISE THE RISER DRAWING TO SHOW THE TANKS |
| MANIFOLDED TOGETHER, AND PROVIDE A DETAIL SHOWING HOW |
| THE PIPING INTERCONNECTION WILL BE MADE- SECTION |
| 6.9.3.9 NFPA 58. PLEASE NOTE THAT PE PIPE CANNOT BE |
| USED FOR PERMANENT INTERCONNECTION OF THE TANKS- |
| SECTION 6.9.3.9B NFPA 58. |
| |
| 3) SHOW HOW THE REGULATOR WILL BE CONNECTED TO THE |
| MANIFOLD- SECTION 6.8.1.1 NFPA 58. |
| |
| NEW COMMENT: |
| 1) I WAS UNABLE TO FIND A PERMIT ON FILE FOR THE |
| EXISTING TANK THAT WAS DESIGNATED TO BE REPLACED AND IS |
| NOW TO BE LEFT IN PLACE ACCORDING TO THE REVISED PLAN. |
| THE TANK SHALL BE REVIEWED AS A NEW INSTALLATION. |
| PLEASE INDICATE THE GALLON SIZE OF THE TANK ON THE |
| PLANS AND SUBMIT MANUFACTURER'S SPECIFICATIONS IN |
| ACCORDANCE WITH SECTION 5.2.1.1 NFPA 58. THE SPECS FOR |
| THE TANK, CATHODIC PROTECTION SYSTEM, AND TANK |
| HOLD-DOWN DETAILS SUBMITTED UNDER THE MASTER PERMIT CAN |
| BE USED IF THOSE SPECS ARE APPLICABLE TO THE EXISTING |
| TANK- SECTIONS 6.6.1.6, 6.6.6.1 NFPA 58. PLEASE PROVIDE |
| NOTES ON THE PLAN TO CLARIFY. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |