2020-10-22 14:22:41 | |
| 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20090641 |
| 10/22/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHOW THE SEPARATION DISTANCE BETWEEN THE TWO |
| UNDERGROUND TANKS. A 3 FT. SEPARATION IS REQUIRED PER |
| TABLE 6.3.1.1 NFPA 58-14. |
| |
| 2) REVISE THE RISER DRAWING TO SHOW THE TANKS |
| MANIFOLDED TOGETHER, AND PROVIDE A DETAIL SHOWING HOW |
| THE PIPING INTERCONNECTION WILL BE MADE- SECTION |
| 6.9.3.9 NFPA 58. PLEASE NOTE THAT PE PIPE CANNOT BE |
| USED FOR PERMANENT INTERCONNECTION OF THE TANKS- |
| SECTION 6.9.3.9B NFPA 58. |
| |
| 3) SHOW HOW THE REGULATOR WILL BE CONNECTED TO THE |
| MANIFOLD- SECTION 6.8.1.1 NFPA 58. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |