2020-10-22 14:22:41 
 1ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090641
 10/22/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHOW THE SEPARATION DISTANCE BETWEEN THE TWO
 UNDERGROUND TANKS. A 3 FT. SEPARATION IS REQUIRED PER
 TABLE 6.3.1.1 NFPA 58-14.
  
 2) REVISE THE RISER DRAWING TO SHOW THE TANKS
 MANIFOLDED TOGETHER, AND PROVIDE A DETAIL SHOWING HOW
 THE PIPING INTERCONNECTION WILL BE MADE- SECTION
 6.9.3.9 NFPA 58. PLEASE NOTE THAT PE PIPE CANNOT BE
 USED FOR PERMANENT INTERCONNECTION OF THE TANKS-
 SECTION 6.9.3.9B NFPA 58.
  
 3) SHOW HOW THE REGULATOR WILL BE CONNECTED TO THE
 MANIFOLD- SECTION 6.8.1.1 NFPA 58.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  