Plan Review Notes For Permit 20090582 |
Permit Number |
20090582 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-09-25 10:11:24 | SKY LIGHT AND FAN | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) SKY LIGHT AND FAN ( SHOW BOTH LOCATIONS) CANNOT BE | | WITHIN 4 FOOT OF THE SIDE OF THE FIREWALL BETWEEN | | TOWNHOUSES FBC R302.2.2 (DRAW THE CENTER LINE BETWEEN | | TOWNHOUSES AND SHOW THE DISTANCE OF THE SKY LIGHT FROM | | THE LINE ON YOUR ROOF PHOTO - WHICH WOULD BE A MINIMUM | | OF 4 FEET 4 INCHES FROM THE CENTER LINE AND THE SIDE OF | | THE SKY LIGHT). | | | | | | | | |
|