2020-09-16 12:06:19 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT- 20090572 |
| 9/16/2020 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE A BASIC SITE PLAN TO SHOW THE LOCATIONS OF |
| THE NEW TANKLESS WATER HEATER- SECTION 107.2.1 WPB. |
| THIS IS A COMMERCIAL PROPERTY WITH PAVED DRIVE AND |
| PARKING AREAS. SHOW HOW THE WATER HEATER WILL BE |
| PROTECTED FROM VEHICULAR IMPACT- SECTION 303.4 FBC FG. |
| |
| 2) HIGHLIGHT THE GPM FLOW RATE SHOWN ON THE SPECS FOR |
| THE SELECTED MODEL AND SUBMIT THE MANUFACTURER'S |
| TEMPERATURE RISE CHART- SECTION 502.1 FBC P. PROVIDE A |
| LIST OF PLUMBING FIXTURES AND THEIR REQUIRED FLOW RATES |
| TO BE SUPPLIED BY THE WATER HEATER- SEE TABLE 604.3 FBC |
| P. THE SPECS SHALL VERIFY THE INTEGRAL RECIRCULATION |
| PUMP WILL HAVE THE CAPACITY TO PROVIDE ADEQUATE FLOW TO |
| THE EXISTING FIXTURES. |
| |
| 3) PROVIDE A WATER DISTRIBUTION RISER DIAGRAM SHOWING |
| THE WATER PIPING TIE-IN CONNECTIONS TO THE NEW WATER |
| HEATER. INDICATE THE TYPES AND SIZES OF HOT, COLD, AND |
| HOT WATER RECIRCULATION PIPES, AND LOCATIONS AND TYPES |
| OF SHUT-OFF VALVES TO BE INSTALLED- SECTIONS 604.3 & |
| 606.1 FBC P. CLARIFY IF A THERMOSTATIC MIXING VALVE IS |
| EXISTING OR TO BE INSTALLED AND SHOW THE WHERE THE HOT |
| WATER RETURN PIPE WILL MAKE CONNECTION BACK INTO THE |
| SYSTEM- SECTION 607.2.2 FBC P. |
| |
| 4) INDICATE THE TYPE AND THICKNESS OF HOT WATER PIPE |
| INSULATION TO BE INSTALLED- SECTION C404.4 FBC EC. |
| |
| 5) REFER TO TABLE C404.2 FBC EC AND HIGHLIGHT OR MARKUP |
| THE EFFICIENCY RATING OF THE NEW WATER HEATER. |
| |
| 6) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION |
| 105.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |