Plan Review Notes
Plan Review Notes For Permit 20090572
Permit Number 20090572
Review Stop P
Sequence Number 1
Notes
Date Text
2020-09-16 12:06:191ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20090572
 9/16/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A BASIC SITE PLAN TO SHOW THE LOCATIONS OF
 THE NEW TANKLESS WATER HEATER- SECTION 107.2.1 WPB.
 THIS IS A COMMERCIAL PROPERTY WITH PAVED DRIVE AND
 PARKING AREAS. SHOW HOW THE WATER HEATER WILL BE
 PROTECTED FROM VEHICULAR IMPACT- SECTION 303.4 FBC FG.
  
 2) HIGHLIGHT THE GPM FLOW RATE SHOWN ON THE SPECS FOR
 THE SELECTED MODEL AND SUBMIT THE MANUFACTURER'S
 TEMPERATURE RISE CHART- SECTION 502.1 FBC P. PROVIDE A
 LIST OF PLUMBING FIXTURES AND THEIR REQUIRED FLOW RATES
 TO BE SUPPLIED BY THE WATER HEATER- SEE TABLE 604.3 FBC
 P. THE SPECS SHALL VERIFY THE INTEGRAL RECIRCULATION
 PUMP WILL HAVE THE CAPACITY TO PROVIDE ADEQUATE FLOW TO
 THE EXISTING FIXTURES.
  
 3) PROVIDE A WATER DISTRIBUTION RISER DIAGRAM SHOWING
 THE WATER PIPING TIE-IN CONNECTIONS TO THE NEW WATER
 HEATER. INDICATE THE TYPES AND SIZES OF HOT, COLD, AND
 HOT WATER RECIRCULATION PIPES, AND LOCATIONS AND TYPES
 OF SHUT-OFF VALVES TO BE INSTALLED- SECTIONS 604.3 &
 606.1 FBC P. CLARIFY IF A THERMOSTATIC MIXING VALVE IS
 EXISTING OR TO BE INSTALLED AND SHOW THE WHERE THE HOT
 WATER RETURN PIPE WILL MAKE CONNECTION BACK INTO THE
 SYSTEM- SECTION 607.2.2 FBC P.
  
 4) INDICATE THE TYPE AND THICKNESS OF HOT WATER PIPE
 INSULATION TO BE INSTALLED- SECTION C404.4 FBC EC.
  
 5) REFER TO TABLE C404.2 FBC EC AND HIGHLIGHT OR MARKUP
 THE EFFICIENCY RATING OF THE NEW WATER HEATER.
  
 6) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  