Plan Review Notes
Plan Review Notes For Permit 20090565
Permit Number 20090565
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2020-12-15 09:46:31THERE ARE NO INDICATIONS OF RESPONSE TO FIRE'S PREVIOUS
 COMMENTS.
  
 THE PREVIOUS COMMENTS FROM FIRE ARE POSTED BELOW,
 PLEASE SPECIFICALLY ADDRESS.
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF FIRE RETARDENT OF THE
 PROPOSED MATERIAL.
  
 PER NFPA 1
  
 25.2.2 FLAME PROPAGATION PERFORMANCE.
 25.2.2.1 ALL TENT FABRIC SHALL MEET THE FLAME
 PROPAGATION
 PERFORMANCE CRITERIA CONTAINED IN TEST METHOD 2 OF NFPA
 701,
 STANDARD METHODS OF FIRE TESTS FOR FLAME PROPAGATION OF
 TEXTILES
 AND FILMS. [101: 11.11.2.1]
 25.2.2.2 ONE OF THE FOLLOWING SHALL SERVE AS EVIDENCE
 THAT THE TENT
 FABRIC MATERIALS HAVE THE REQUIRED FLAME PROPAGATION
 PERFORMANCE:
 (1) THE AHJ SHALL REQUIRE A CERTIFICATE OR OTHER
 EVIDENCE OF
 ACCEPTANCE BY AN ORGANIZATION ACCEPTABLE TO THE AHJ.
 (2) THE AHJ SHALL REQUIRE A REPORT OF TESTS MADE BY
 OTHER
 INSPECTION AUTHORITIES OR ORGANIZATIONS ACCEPTABLE TO
 THE
 AHJ. [101: 11.11.2.2]
  
 PLEASE PROVIDE THE REQUIRED DOCUMENTATION
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  