Plan Review Notes
Plan Review Notes For Permit 20090565
Permit Number 20090565
Review Stop B
Sequence Number 2
Notes
Date Text
2020-12-17 13:56:55PLAN
 REVIEW COMMENTS
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) PARTIALLY ADDRESSED. (SPECIFY THE HEIGHT OF THE
 POLES. THE POLES ARE REQUIRED TO COMPLY WITH FBC
 3105.4.2 DESIGN OF THE STRUCTURAL FRAMING MEMBERS SHALL
 BE BASED ON RATIONAL ANALYSIS, USING THE APPLICABLE
 WIND LOADS OF CHAPTER 16 AS SHOWN BELOW: 3105.4.2.1 THE
 WIND DESIGN LOADS FOR ANY FABRIC OR MEMBRANE-COVERED
 STRUCTURE DESIGNED WITH A QUICK REMOVAL OR BREAKAWAY
 MEMBRANE OR FABRIC AT WIND VELOCITIES OF 75 MPH, SHALL
 BE BASED ON THE FOLLOWING CRITERIA: 1.MINIMUM WIND
 SPEED 105 MPH 2.EXPOSURE CATEGORY B, C OR D AS DEFINED
 IN CHAPTER 16.THE POLES WITH THE FABRIC REMOVED ARE
 REQUIRED TO BE CAPABLE OF WITHSTANDING 170 MPH
 WINDSPEED IN EXPOSURE C.) SUBMIT SIGNED AND SEALED
 DRAWINGS FROM A FLORIDA LICENSED DESIGN PROFESSIONAL
 THAT PROVIDE STRUCTURAL DETAILS FOR THE POLES AND THEIR
 FOUNDATIONS. SPECIFY THE HEIGHT AND DIMENSIONS OF THE
 POLES. PROVIDE THE DIMENSIONS OF THE FOUNDATIONS.
 SPECIFY THE WIND DESIGN DATA ON THE DRAWINGS AND
 PROVIDE CALCULATIONS. FS 471 OR 481, FBC 107, 1609 &
 3105.3
  
 3) NOT ADDRESSED. (BASED ON THE PLANS IT APPEARS THAT
 THE SAILS WILL HAVE TO BE REMOVED WHEN THE WIND SPEED
 IS FORCAST TO EXCEED 75 MPH.) IF THE SHADE SAILS ARE
 REQUIRED TO BE REMOVED DURING HIGH WIND EVENTS, SPECIFY
 WHEN THEY ARE TO BE REMOVE AND PROVIDE DETAILED REMOVAL
 INSTRUCTIONS WITH PHOTOGRAPHS/DRAWINGS THAT SHOW HOW
 THIS IS DONE IN TERMS THAT A LAYMAN WILL UNDERSTAND.
 THESE INSTRUCTIONS ARE TO BE PROVIDED TO THE PROPERTY
 OWNER, OWNER'S REPRESENTATIVE OR LESSEE. FBC 107.2.1
  
 4) SUBMIT THE FLAME SPREAD EVALUATION FOR THE SHADE
 SAIL FABRIC. FBC 3105.3.4.1 FABRIC USED FOR AWNINGS OR
 FABRIC-COVERED FRAMES SHALL MEET THE FLAME PROPAGATION
 PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A FLAME SPREAD
 INDEX NOT GREATER THAN 25 WHEN TESTED IN ACCORDANCE
 WITH ASTM E84 OR UL 723.
  
 5) COMPLIED.
  
 6) THE VALUE OF $100.00 IS LOW FOR THIS PROJECT. FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 7) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  
  