2020-10-02 08:51:26 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SUBMIT A SURVEY AND A SITE PLAN SHOWING THE |
| LOCATIONS OF THE METAL POLES THAT SUPPORT THE CABLES |
| AND THE SHADE SAIL FABRIC. FBC 107.2.1 |
| |
| 2) SUBMIT SIGNED AND SEALED DRAWINGS FROM A FLORIDA |
| LICENSED DESIGN PROFESSIONAL THAT PROVIDE STRUCTURAL |
| DETAILS FOR THE POLES AND THEIR FOUNDATIONS. SPECIFY |
| THE HEIGHT AND DIMENSIONS OF THE POLES. PROVIDE THE |
| DIMENSIONS OF THE FOUNDATIONS. SPECIFY THE WIND DESIGN |
| DATA ON THE DRAWINGS AND PROVIDE CALCULATIONS. FS 471 |
| OR 481, FBC 107, 1609 & 3105.3 |
| |
| 3) IF THE SHADE SAILS ARE REQUIRED TO BE REMOVED DURING |
| HIGH WIND EVENTS, SPECIFY WHEN THEY ARE TO BE REMOVE |
| AND PROVIDE DETAILED REMOVAL INSTRUCTIONS WITH |
| PHOTOGRAPHS/DRAWINGS THAT SHOW HOW THIS IS DONE IN |
| TERMS THAT A LAYMAN WILL UNDERSTAND. THESE INSTRUCTIONS |
| ARE TO BE PROVIDED TO THE PROPERTY OWNER, OWNER'S |
| REPRESENTATIVE OR LESSEE. FBC 107.2.1 |
| |
| 4) SUBMIT THE FLAME SPREAD EVALUATION FOR THE SHADE |
| SAIL FABRIC. FBC 3105.3.4.1 FABRIC USED FOR AWNINGS OR |
| FABRIC-COVERED FRAMES SHALL MEET THE FLAME PROPAGATION |
| PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A FLAME SPREAD |
| INDEX NOT GREATER THAN 25 WHEN TESTED IN ACCORDANCE |
| WITH ASTM E84 OR UL 723. |
| |
| 5) SPECIFY THE HEIGHT OF THE SAIL SHADES ABOVE GRADE. |
| FBC 107.2.1 |
| |
| 6) THE VALUE OF $100.00 IS LOW FOR THIS PROJECT. FBC |
| 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| |
| |
| |
| |