Plan Review Notes
Plan Review Notes For Permit 20090559
Permit Number 20090559
Review Stop G
Sequence Number 2
Notes
Date Text
2020-11-18 16:29:052ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090559
 11/18/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENT #2 FROM THE 1ST REVIEW WAS NOT ADDRESSED-
 PLEASE COMPLY.
  
 2) SHEET 1: THE UG LP TANK INSTALLATION DETAIL HAS A
 COPIED ENGINEER'S SEAL AND SIGNATURE FROM 7/11/10.
 PLEASE SUBMIT AN UPDATED DOCUMENT WITH AN ELECTRONIC
 SEAL AND SIGNATURE, OR IF THE EOR DOES NOT HAVE AN
 ELECTRONIC SEAL AND SIGNATURE, A HARD PAPER COPY WITH A
 RAISED OR INK SEAL AND WET SIGNATURE CAN BE DROPPED OFF
 IN THE DROP BOX AT WPB CITY HALL WITH AN ATTACHED PLAN
 REVIEW REQUEST FORM- FL. STATUTE 471.025 AND SECTIONS
 61G15-23.002-23.005 FAC. PLEASE SHOW ON THE DETAIL HOW
 THE TANK WILL BE PROTECTED FROM ABRASION AND CORROSION
 FROM THE TIE DOWN CABLES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  