2020-11-18 16:29:05 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20090559 |
| 11/18/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| COMMENT #2 FROM THE 1ST REVIEW WAS NOT ADDRESSED- |
| PLEASE COMPLY. |
| |
| 2) SHEET 1: THE UG LP TANK INSTALLATION DETAIL HAS A |
| COPIED ENGINEER'S SEAL AND SIGNATURE FROM 7/11/10. |
| PLEASE SUBMIT AN UPDATED DOCUMENT WITH AN ELECTRONIC |
| SEAL AND SIGNATURE, OR IF THE EOR DOES NOT HAVE AN |
| ELECTRONIC SEAL AND SIGNATURE, A HARD PAPER COPY WITH A |
| RAISED OR INK SEAL AND WET SIGNATURE CAN BE DROPPED OFF |
| IN THE DROP BOX AT WPB CITY HALL WITH AN ATTACHED PLAN |
| REVIEW REQUEST FORM- FL. STATUTE 471.025 AND SECTIONS |
| 61G15-23.002-23.005 FAC. PLEASE SHOW ON THE DETAIL HOW |
| THE TANK WILL BE PROTECTED FROM ABRASION AND CORROSION |
| FROM THE TIE DOWN CABLES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |