Plan Review Notes For Permit 20090559 |
Permit Number |
20090559 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-11-23 14:23:03 | PLAN REVIEW GENERATOR / ELECTRICAL | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | NEC 2014 | | | | 2ND REVIEW COMMENTS FROM 1ST REVIEW HAVE NOT BEEN | | ADDRESSED | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1) PROVIDE SPECIFICATIONS FOR AUTOMATIC TRANSFER | | SWITCH. (ATS) | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | NOTE: THE ATS SPECIFICATIONS MAY BE INCLUDED IN THE | | GENERATOR SPECIFICATIONS. THE GENERATOR SPECIFICATIONS | | SUBMITTED FOR REVIEW ARE INCOMPLETE. | | IF NECESSARY, PROVIDE SEPERATE ATS SPEC'S. | | | | | | | | |
|