2020-11-23 14:23:03PLAN REVIEW GENERATOR / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 2ND REVIEW COMMENTS FROM 1ST REVIEW HAVE NOT BEEN
 ADDRESSED
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE SPECIFICATIONS FOR AUTOMATIC TRANSFER
 SWITCH. (ATS)
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 NOTE: THE ATS SPECIFICATIONS MAY BE INCLUDED IN THE
 GENERATOR SPECIFICATIONS. THE GENERATOR SPECIFICATIONS
 SUBMITTED FOR REVIEW ARE INCOMPLETE.
 IF NECESSARY, PROVIDE SEPERATE ATS SPEC'S.
  
  
  
  