Plan Review Notes
Plan Review Notes For Permit 20090559
Permit Number 20090559
Review Stop SIGNATURE
Sequence Number 1
Notes
Date Text
2020-10-19 09:58:40PLAN REVIEW GENERATOR / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DESIGN PROFESSIONALS
  
 RE: PRE-CAST GENRATOR PAD ENGINEERING
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  
 CONTRACTORS
  
 RE: ELECTRIC RISER AND NEW LOAD CALCULATIONS
  
 1. A CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE
 THEIR NAME, LICENSE NUMBER AND SIGNATURE ON PLAN SHEETS
 UNDER THEIR AUTHORITY ?
 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, SECTION 107.2.1.
  
 2. EITHER UPLOAD DOCUMENTS VIA THE PROJECTDOX PORTAL
 WITH SIGNATURE OF CONTRACTOR OR DESIGNER AS APPLICABLE;
 USE THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT;
 OR DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH
 CONTRACTORS OR DESIGNERS SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  
  
  
2020-10-05 17:39:13SIGNATURE REVIEW
 CCOLE
 10/05/2020
  
 DENIED.
  
 1) THE AMERICAST GENERATOR PAD SPECIFICATIONS, AND THE
 UG LP TANK INSTALLATION DETAIL EACH HAVE COPIED
 ENGINEER'S SEAL AND SIGNATURES. THE LP TANK
 CERTIFICATION IS BACKDATED FROM 7/11/10. PLEASE SUBMIT
 DOCUMENTS BEARING THE CURRENT ELECTRONIC SEALS AND
 SIGNATURES OF THE ENGINEERS. ALTERNATIVELY, IF THE
 ENGINEER DOES NOT HAVE AN ELECTRONIC SEAL AND
 SIGNATURE, A HARD PAPER COPY WITH A RAISED OR INK SEAL
 AND WET SIGNATURE CAN BE DROPPED OFF IN THE DROP BOX AT
 WPB CITY HALL WITH AN ATTACHED PLAN REVIEW REQUEST
 FORM- FL. STATUTE 471.025 AND SECTIONS
 61G15-23.002-23.005 FAC.
  
 2) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE GAS
 RISER DRAWING SHALL PROVIDE HIS SIGNATURE ON IT-
 SECTION 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H)
 & 471.025.