Plan Review Notes
Plan Review Notes For Permit 20090559
Permit Number 20090559
Review Stop G
Sequence Number 1
Notes
Date Text
2020-10-05 17:34:121ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090559
 10/5/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SURVEY: PLEASE SHOW THE CLEARANCE DISTANCE FROM THE
 TANK LP TANK TO THE DRIVEWAY- SECTIONS 6.6.1.1 &
 6.6.6.1 NFPA 54.
  
 2) SHEET 1: THE UG LP TANK INSTALLATION DETAIL HAS A
 COPIED ENGINEER'S SEAL AND SIGNATURE FROM 7/11/10.
 PLEASE SUBMIT AN UPDATED DOCUMENT WITH AN ELECTRONIC
 SEAL AND SIGNATURE, OR IF THE EOR DOES NOT HAVE AN
 ELECTRONIC SEAL AND SIGNATURE, A HARD PAPER COPY WITH A
 RAISED OR INK SEAL AND WET SIGNATURE CAN BE DROPPED OFF
 IN THE DROP BOX AT WPB CITY HALL WITH AN ATTACHED PLAN
 REVIEW REQUEST FORM- FL. STATUTE 471.025 AND SECTIONS
 61G15-23.002-23.005 FAC. PLEASE SHOW ON THE DETAIL HOW
 THE TANK WILL BE PROTECTED FROM ABRASION AND CORROSION
 FROM THE TIE DOWN CABLES.
  
 3) SUBMIT SPECS FOR THE NEW GAS RANGE THAT INDICATE THE
 BTUH LOAD AND GAS INPUT PRESSURE- SECTION 107.2.1 WPB.
  
 4) INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO THE
 NEW RANGE AND PROVIDE COMBUSTION AIR CALCULATIONS-
 SECTION G2407.1 FBC RES. PLEASE NOTE IF USING INDOOR
 AIR SEE SECTION G2407.5.
  
 5) INDICATE HOW THE NEW RANGE WILL BE VENTED. CLARIFY
 IF THERE IS AN EXISTING RANGE HOOD OR IF A NEW HOOD AND
 EXHAUST SYSTEM WILL BE INSTALLED- SECTION M1503 FBC
 RES. AND SECTION 107.2.1 WPB. PLEASE NOTE THAT NEW
 RANGE HOODS AND EXHAUST DUCTS WILL REQUIRE PLANS AND
 SPECIFICATIONS TO BE SUBMITTED, AND A MECHANICAL SUB OR
 PRIMARY PERMIT MUST BE OBTAINED- SECTION 105.1 WPB.
  
 6) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE GAS
 RISER DRAWING SHALL PROVIDE HIS/HER SIGNATURE ON IT-
 SECTION 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H)
 & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  