Plan Review Notes For Permit 20090541 |
Permit Number |
20090541 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-09-16 09:40:11 | REVISION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE SHOW THE LOCATION OF THE SHUTTER (INTERIOR OR | | EXTERIOR) - EXTERIOR REQUIRES A COMPLETE PRODUCT | | APPROVAL (MIAMI DADE OR FLORIDA STATE - FRONT PAGES) | | 2) SHOW SHUTTER OPENING SIZE AND REQUIRED DESIGN | | PRESSURES. | | 3) ALTERNATE REBAR CONNECTION DRAWING - NEEDS TO BE | | SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER. |
|