Plan Review Notes For Permit 20090529 |
Permit Number |
20090529 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-10-08 13:17:40 | PLAN REVIEW GENERATOR / BUILDING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | RE: PRE-CAST GENERATOR PAD ENGINEERING: | | | | 1. THE WEIGTH OF THE PROPOSED 2020 GENERAC POWER | | SYSTEMS, INC. MODEL G007042-3, G007043-3, 22KW | | GENERATOR IS 445LBS. | | | | THE WEIGTH OF THE PROPOSED GENERAC 007042 & 7043, 22KW | | GENERATOR REFRENCED ON THE PRE-CAST PAD ENGINEERING IS | | 466LBS. (SEE GENERATOR TABLE) | | | | NOTE: THE WEIGHT OF THE GENERATOR EFFECTS THE DESIGN | | WIND LOADS OF THE GENERATOR. THE DESIGN WIND LOADS OF | | THE GENERATOR MUST MEET THE REQUIREMENTS OF THE | | SITE-SPECIFIC DESIGN WIND LOADS PROVIDED. | | (SEE WIND DESIGN REQUIREMENTS PER ASCE 7-10) | | | | SUBMIT NEW PRE-CAST PAD ENGINEERING USING THE WEIGHT OF | | THE PROPOSED GENERATOR. | | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | | | |
|