2020-10-08 13:17:40PLAN REVIEW GENERATOR / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PRE-CAST GENERATOR PAD ENGINEERING:
  
 1. THE WEIGTH OF THE PROPOSED 2020 GENERAC POWER
 SYSTEMS, INC. MODEL G007042-3, G007043-3, 22KW
 GENERATOR IS 445LBS.
  
 THE WEIGTH OF THE PROPOSED GENERAC 007042 & 7043, 22KW
 GENERATOR REFRENCED ON THE PRE-CAST PAD ENGINEERING IS
 466LBS. (SEE GENERATOR TABLE)
  
 NOTE: THE WEIGHT OF THE GENERATOR EFFECTS THE DESIGN
 WIND LOADS OF THE GENERATOR. THE DESIGN WIND LOADS OF
 THE GENERATOR MUST MEET THE REQUIREMENTS OF THE
 SITE-SPECIFIC DESIGN WIND LOADS PROVIDED.
 (SEE WIND DESIGN REQUIREMENTS PER ASCE 7-10)
  
 SUBMIT NEW PRE-CAST PAD ENGINEERING USING THE WEIGHT OF
 THE PROPOSED GENERATOR.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  
  