Plan Review Notes For Permit 20090509 |
Permit Number |
20090509 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-11-06 08:30:46 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) I HAVE NO IDEA WHAT YOU ARE GOING TO BE INSTALLING. | | THERE ARE MULTIPLE PRODUCT APPROVALS FROM DIFFERENT | | MANUFACTURERS FOR THE (1) DOOR AND FOR THE SAME WINDOW | | TYPE. YOU WILL NEED TO PUT THE PRODUCT APPROVAL NUMBER | | IN THE INSTALLATION SCHEDULE FOR EACH WINDOW OPENING TO | | CLARIFY. FBC 107.2 | | | | 2) THERE IS NO PRODUCT APPROVALS FOR THE ROLL DOWN | | SHUTTERS. I WILL ALSO NEED AN INSTALLATION SCHEDULE FOR | | THE ROLL DOWN SHUTTERS WITH REQUIRED GLASS SEPARATION, | | SHUTTER SPAN, ANCHOR TYPE, ANCHOR SPACING AND ANY OTHER | | DETAILS NEEDED TO DETERMINE IF THEY WILL MEET THE | | REQUIRED WIND LOADS. FBC 107.2 AND FBC-R301.2.1.2 | | |
|