Plan Review Notes For Permit 20090509 |
Permit Number |
20090509 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-09-28 14:58:11 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC - R 301.2.1.2 SUBMIT AN INSTALLATION SCHEDULE | | FOR THE STORM PANELS. SPECIFY THE OPENING SIZE, THE | | WIND PRESSURES, TYPE OF ANCHOR, ANCHOR SPACING, EDGE | | DISTANCE, PANEL LENGTH, PANEL SPAN, SEPARATION DISTANCE | | FROM PANEL TO GLASS AND THE APPLICABLE SECTION NUMBER | | FROM THE INSTALLATION DRAWINGS. |
|